- baud rate:
- 10/100 Mbit/s
- color:
- Dark gray
- communication:
- EtherNet/IPTM
- conformity marking:
- CE
- connection technology communication fieldbus:
- EtherNet/IPTM: 2 x RJ-45
- connection technology device configuration:
- 1 x Male connector: 4-pole
- connection technology system supply:
- 2 x CAGE CLAMP
- connection type 1:
- System supply
- country of origin sales organisation germany:
- DE
- depth:
- 71.9 mm / 2.831 inch
- depth from upper edge of din rail:
- 64.7 mm / 2.547 inch
- derating:
- Derating (supply voltage): Surrounding air temperatures under laboratory conditions: (-25 +30 %): for -40 +55 C: 24 V (-25 +20 %): for +55 +70 C: 24 V (-25 +10 %): Lower limit in all temperature ranges: 27.5 % (
- emc emission of interference:
- Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
- emc immunity to interference:
- Per EN 61000-6-1, -2: EN 61131-2: marine applications: EN 50121-3-2: EN 50121-4, -5: EN 60255-26: EN 60870-2-1: EN 61850-3: IEC 61000-6-5: IEEE 1613: VDEW: 1994
- ethernet protocols:
- HTTP(S) || BootP || DHCP || DNS || SNTP || FTP(S) || SNMP
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.25 1.5 mm / 24 16 AWG
- fire load:
- 0.171 MJ
- height:
- 96.8 mm / 3.811 inch
- housing material:
- Polycarbonate: polyamide 6.6
- input and output fieldbus process image max:
- 1020 Worte/1020 Worte
- input current typ at nominal load 24 v:
- 280 mA
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- number of modules per node max:
- 64
- operating altitude:
- Without temperature derating: 0 2000 m: with temperature derating: 2000 5000 m (0.5 K/100 m): 5000 m (max.)
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per IEC 61131-2
- power consumption 5 v system supply:
- 350 mA
- power supply efficiency typ at nominal load 24 v:
- 0.9
- protection type:
- IP20
- rated surge voltage:
- 1 kV
- relative humidity with condensation:
- Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
- relative humidity without condensation:
- 0.95
- shock resistance:
- Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks: 25g/6 ms/1,000 shocks), EN 50155, EN 61373
- solid conductor:
- 0.25 1.5 mm / 24 16 AWG
- strip length:
- 5 6 mm / 0.2 0.24 inch
- supply voltage system:
- 24 VDC: via pluggable connector (CAGE CLAMP connection): Derating must be observed!
- surrounding air temperature operation:
- -40 70 C
- surrounding air temperature storage:
- -40 85 C
- total current system supply:
- 700 mA
- transmission medium:
- Twisted Pair S-UTP: 100 : Cat. 5: 100 m maximum cable length
- transmission performance:
- Class D per EN 50173
- vibration resistance:
- Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155: EN 61373
- weight:
- 103.941 g
- width:
- 49.5 mm / 1.949 inch