ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc: II (1) D [Ex ia Da] IIIC: I (M1) [Ex ia Ma] I
mounting position:
Horizontal (standing/lying): vertical
mounting type:
DIN-35 rail
note:
The digital input module must only be operated with a 24 VDC Ex i power supply!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!
number of digital inputs:
8
number of incoming power jumper contacts:
2
number of outgoing power jumper contacts:
2
open circuit voltage:
8.2 V
operating altitude:
0 2000 m
output internal data width max:
16 bits
packaging type:
Box
permissible h2s contaminant concentration at a relative humidity 75:
10 ppm
permissible so2 contaminant concentration at a relative humidity 75:
25 ppm
pollution degree 5:
2 per IEC 61131-2
power consumption 5 v system supply:
56 mA
power consumption field supply module with no external load:
11 mA
power consumption pmax:
1.2 W
power loss pl:
0.54 W
protection type:
IP20
reactances ex ia i:
Lo = 100 mH: Co = 30 F
reactances ex ia iia:
Lo = 100 mH: Co = 39 F
reactances ex ia iib:
Lo = 100 mH: Co = 9.9 F
reactances ex ia iic:
Lo = 100 mH: Co = 1 F
reactances note:
Reactances without accounting for the concurrence of L and C
relative humidity without condensation:
0.95
safety relevant data circuit:
Uo = 11.76 V: Io = 12.4 mA: Po = 36.67 mW: Linear characteristic curve
sensor connection:
4 x (2-wire)
shock resistance:
15g per IEC 60068-2-27
short circuit current:
ยค 8.2 mA ( 0.2 mA)
signal current 0 namur:
1.2 mA
signal current 1 namur:
2.1 mA
signal type:
NAMUR
solid conductor:
0.08 2.5 mm / 28 14 AWG
strip length:
8 9 mm / 0.31 0.35 inch
supply voltage field:
24 VDC: (Ex i power supply: UO = max. 27.3 V): via power jumper contacts (power supply via blade contact: transmission via spring contact)
Double-deck male headers; Angled solder pin 1 x 1 mm; 9 x 2-pole; Pin spacing 3.81 mm / 0.15 in; 100% protected against mismating; with support; Horizontal PCB mounting