Wago

WAGO 750-481/040-000

(No reviews yet) Write a Review
SKU:
750-481/040-000
MPN:
750-481/040-000
Condition:
New
color:
Blue
conformity marking:
CE
connection technology inputs outputs:
16 x CAGE CLAMP
connection type 1:
Inputs/outputs
conversion time:
150 500 ms (per channel)
conversion time typ:
325 ms
country of origin sales organisation germany:
DE
current carrying capacity power jumper contacts:
0.0416666666666667
data width:
2 x 16-bit data: 2 x 8-bit control/status (optional)
depth:
67.8 mm / 2.669 inch
depth from upper edge of din rail:
60.6 mm / 2.386 inch
dielectric strength:
510 VAC/775 VDC: per EN 60870-2-1
emc emission of interference:
Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3
emc immunity to interference:
Per EN 61000-6-1, -2, EN 61131-2, marine applications, EN 60255-26, EN 60870-2-1, EN 61850-3, IEC 61000-6-5, IEEE 1613, VDEW: 1994
ex guideline:
EN/IEC 60079-0, -7, -11
exposure to pollutants:
Per IEC 60068-2-42 and IEC 60068-2-43
fine stranded conductor:
0.25 2.5 mm / 24 14 AWG
fire load:
1.249 MJ
height:
100 mm / 3.937 inch
housing material:
Polycarbonate: polyamide 6.6
intrinsic safety ex i:
Yes
isolation:
300 VAC system/field
marking:
ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc: II (1) D [Ex ia Da] IIIC: I (M1) [Ex ia Ma] I
measured current typ:
< 0.5 mA
measurement error deviation max from the upper range value:
0.002
measurement error reference temperature:
25 C
mounting position:
Horizontal (standing/lying): vertical
mounting type:
DIN-35 rail
note:
The analog output module must only be operated via 24 VDC Ex i XTR power supply (750-606/040-000)!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 XTR manuals!
number of analog inputs:
2
number of incoming power jumper contacts:
2
number of outgoing power jumper contacts:
2
operating altitude:
Without temperature derating: 0 2000 m: with temperature derating: 2000 5000 m (0.5 K/100 m): 5000 m (max.)
packaging type:
Box
permissible h2s contaminant concentration at a relative humidity 75:
10 ppm
permissible so2 contaminant concentration at a relative humidity 75:
25 ppm
pollution degree 5:
2 per IEC 61131-2
power consumption 5 v system supply:
25 mA
power consumption field supply module with no external load:
12 mA
power consumption pmax:
0.45 W
power loss pl:
0.45 W
protection type:
IP20
rated surge voltage:
1 kV: Rated surge voltage between intrinsically safe and non-intrinsically safe circuits: 1.5 kV (EN 60079-11)
reactances ex ia i:
Lo = 100 mH: Co = 1000 F
reactances ex ia iia:
Lo = 100 mH: Co = 1000 F
reactances ex ia iib:
Lo = 100 mH: Co = 240 F
reactances ex ia iic:
Lo = 100 mH: Co = 13.5 F
reactances note:
Reactances without accounting for the concurrence of L and C
relative humidity with condensation:
Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
relative humidity without condensation:
0.95
resolution over entire range:
0.1 C, 0.1 , 0.0049 %
safety relevant data circuit:
Uo = 7.2 V: Io = 5.8 mA: Po = 10.5 mW: Linear characteristic curve
sensor connection:
2 x (2-wire, 3-wire)
sensor types:
Pt100: Configurable: Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000: Resistors: 1.2 k, 5 k: Potentiometer setting 0 100 %: 1k2, 5k0
shock resistance:
Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks: 25g/6 ms/1,000 shocks), EN 61373
signal type:
Resistance measurement || Potentiometer positions
signal type configurable:
Yes
solid conductor:
0.25 2.5 mm / 24 14 AWG
strip length:
8 9 mm / 0.31 0.35 inch
supply voltage field:
24 VDC: (Ex i XTR power supply: UO = max. 26.8 V): via power jumper contacts (power supply via blade contact: transmission via spring contact)
supply voltage system:
5 VDC: via data contacts
surrounding air temperature operation:
-40 70 C
surrounding air temperature storage:
-40 85 C
temperature error max of the upper range value:
0.01 %/K
temperature range:
200 +850 C (Pt), 60 +250 C (Ni), 80 +320 C (Ni120)
total number of channels module:
2
vibration resistance:
Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3
weight:
90.600 g
width:
24 mm / 0.945 inch
  • Wago 750-481/040-000
  • Wago 750-481/040-000
  • Wago 750-481/040-000
$1,173.00

Description

2-channel analog input; Resistance measurement; Intrinsically safe; Extreme.

The WAGO 750 XTR series intrinsically-safe analog input slice module is designed for extended temperature ranges and features two configurable analog inputs for RTD sensors (Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000) and potentiometers (1.2k?, 5k?) with 0.1°C resolution and 325ms conversion time. It operates on a 5V DC supply provided by the system and includes spring CAGE CLAMP connections for secure wiring. The module is mounted on a DIN-35 rail, has a width of 24mm, and is rated for ambient temperatures between -40°C and +70°C, with an IP20 protection rating, equivalent to model 750481040000.