WAGO 750-485

(No reviews yet) Write a Review
SKU:
750-485
MPN:
750-485
Condition:
New
color:
Blue
conformity marking:
CE
connection technology inputs outputs:
16 x CAGE CLAMP
connection type 1:
Inputs/outputs
conversion time typ:
2 ms
country of origin sales organisation germany:
DE
data width:
2 x 16-bit data: 2 x 8-bit control/status (optional)
depth:
67.8 mm / 2.669 inch
depth from upper edge of din rail:
60.6 mm / 2.386 inch
emc emission of interference:
Per EN 61000-6-3, marine applications
emc immunity to interference:
Per EN 61000-6-2, marine applications
ex guideline:
EN IEC 60079-0, -7, -11
exposure to pollutants:
Per IEC 60068-2-42 and IEC 60068-2-43
fine stranded conductor:
0.08 2.5 mm / 28 14 AWG
fire load:
2.027 MJ
height:
100 mm / 3.937 inch
housing material:
Polycarbonate: polyamide 6.6
input resistance max:
100
intrinsic safety ex i:
Yes
isolation:
300 VAC system/field
marking:
ATEX, IECEx, INMETRO, Underwriters Laboratories Inc.
measurement error deviation max from the upper range value:
0.002
measurement error reference temperature:
25 C
mounting position:
Horizontal (standing/lying): vertical
mounting type:
DIN-35 rail
note:
The analog output module must only be operated via 24 VDC Ex i!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!
number of analog inputs:
2
number of incoming power jumper contacts:
2
number of outgoing power jumper contacts:
2
operating altitude:
0 2000 m
packaging type:
Box
permissible h2s contaminant concentration at a relative humidity 75:
10 ppm
permissible so2 contaminant concentration at a relative humidity 75:
25 ppm
pollution degree 5:
2 per IEC 61131-2
power consumption 5 v system supply:
31 mA
power consumption field supply module with no external load:
11 mA
power consumption pmax:
1.3 W
power loss pl:
0.75 W
protection type:
IP20
reactances ex ia i:
Lo = 100 mH: Co = 3.5 F
reactances ex ia iia:
Lo = 40 mH: Co = 2.2 F
reactances ex ia iib:
Lo = 18 mH: Co = 680 nF
reactances ex ia iic:
Lo = 5 mH: Co = 88 nF
reactances note:
Reactances without accounting for the concurrence of L and C
relative humidity without condensation:
0.95
resolution bit:
12 bits
safety relevant data circuit:
Uo = 27.3 V: Io = 90 mA: Po = 0.61 W: Linear characteristic curve
sensor connection:
2 x (3-wire)
shock resistance:
15g per IEC 60068-2-27
signal characteristic:
Single-ended
signal type:
Current
signal type current:
4 20 mADC
solid conductor:
0.08 2.5 mm / 28 14 AWG
strip length:
8 9 mm / 0.31 0.35 inch
supply voltage field:
24 VDC: (Ex i power supply: UO = max. 27.3 V): via power jumper contacts (power supply via blade contact: transmission via spring contact)
supply voltage sensor:
16 VDC: Transmitter supply UV at 20 mA
supply voltage system:
5 VDC: via data contacts
surrounding air temperature operation:
0 55 C
surrounding air temperature storage:
-40 85 C
temperature error max of the upper range value:
0.01 %/K
total number of channels module:
2
vibration resistance:
4g per IEC 60068-2-6
weight:
97.647 g
width:
24 mm / 0.945 inch
$984.30

Description

2-channel analog input; 2- to 4-conductor connection; Single-ended; Intrinsically safe

  • Green LED (signal current on/off)
  • Red LED (wire breakage, measurement range overflow/underflow)
View AllClose