2 x (2-wire, 3-wire): A suitable field side connection module (e.g., 750-614) must also be used to connect other actuators.
color:
Light gray
conformity marking:
CE
connection technology inputs outputs:
8 x CAGE CLAMP
connection type 1:
Inputs/outputs
country of origin sales organisation germany:
DE
current carrying capacity power jumper contacts:
0.416666666666667
depth:
69.8 mm / 2.748 inch
depth from upper edge of din rail:
62.6 mm / 2.465 inch
emc emission of interference:
Per EN 61000-6-4, marine applications
emc immunity to interference:
Per EN 61000-6-2, marine applications
exposure to pollutants:
Per IEC 60068-2-42 and IEC 60068-2-43
fine stranded conductor:
0.08 2.5 mm / 28 14 AWG
fire load:
0.924 MJ
height:
100 mm / 3.937 inch
housing material:
Polycarbonate: polyamide 6.6
indicators:
LED (A-D) green: Status DO 1 DO 4
inductive load switch off energy dissipation max:
0.3 J
interference free with safety function:
Yes
isolation:
500 V system/field
load type:
Resistive, inductive, lamp load
mounting position:
Horizontal (standing/lying): vertical
mounting type:
DIN-35 rail
number of digital outputs:
4
number of incoming power jumper contacts:
2
number of outgoing power jumper contacts:
2
operating altitude:
0 2000 m
output characteristic:
High-side switching
output current:
Short-circuit-protected
output current per channel:
0.5 A
output internal data width max:
4 bits
packaging type:
Box
permissible h2s contaminant concentration at a relative humidity 75:
10 ppm
permissible so2 contaminant concentration at a relative humidity 75:
25 ppm
pollution degree 5:
2 per IEC 61131-2
power consumption 5 v system supply:
10 mA
power consumption field supply module with no external load:
30 mA
protection type:
IP20
relative humidity with condensation:
Short-term condensation per Class 3K6/IEC EN 60721-3-3 and E-DIN 40046-721-3, accounting for a temperature range of 20 to +60 C (except for wind-driven precipitation, water and ice formation)
relative humidity without condensation:
0.95
shock resistance:
15g per IEC 60068-2-27
signal type:
Voltage
solid conductor:
0.08 2.5 mm / 28 14 AWG
strip length:
8 9 mm / 0.31 0.35 inch
supply voltage field:
24 VDC (-25 +30 %): via power jumper contacts (power supply via blade contact: transmission via spring contact)
4-channel digital output; 24 VDC; 0.5 A; Ext. Temperature. The WAGO 750 series standard DC digital output slice module features four digital outputs (24Vdc, 0.5A each) with high-side switching and...
4-channel digital output; 24 VDC; 0.5 A; Interference-free. The WAGO 750 series standard DC digital output slice module is an interference-free version featuring 4 digital outputs (24Vdc, 500mA...
4-channel digital output; 24 VDC; 0.5 A. The WAGO 750 series standard DC digital output slice module (750504) features 4 digital outputs (24Vdc, 0.5A each) with high-side switching and supports both...
4-channel analog input; Single-ended; Ext. Temperature. The WAGO 750 series standard analog input slice module is designed for extended temperature ranges and features four common ground potential...
4-channel digital input; 24 VDC; 3 ms; Ext. Temperature. The WAGO 750 series standard DC digital input slice module is designed for extended temperature ranges and features 4 digital inputs (24Vdc...
Controller PFC100; 2 x ETHERNET; Ext. Temperature. The WAGO PFC100 series PLC CPU unit is designed for extended temperature ranges and features an ARM Cortex-A8 600MHz processor with 256MB RAM and...