DALI Specification: DIN IEC 60929 (VDE 0712 Part 23) only in connection with 288-895 DC/DC Converter: DSI Specification: TRIDONIC ATCO Specification 2.0
emc emission of interference:
Per EN 61000-6-3*, marine applications, *only in connection with 288-895 DC/DC Converter
emc immunity to interference:
Per EN 61000-6-2*, marine applications, *only in connection with 288-895 DC/DC Converter
exposure to pollutants:
Per IEC 60068-2-42 and IEC 60068-2-43
fire load:
0.948 MJ
height:
69.8 mm / 2.748 inch
height from upper edge of din rail:
62.6 mm / 2.465 inch
housing material:
Polycarbonate: polyamide 6.6
isolation:
1500 VDC DALI bus/Internal data bus
mounting position:
Horizontal (standing/lying): vertical
mounting type:
DIN-35 rail
number of incoming power jumper contacts:
2
number of outgoing power jumper contacts:
2
operating altitude:
0 2000 m
packaging type:
Box
permissible h2s contaminant concentration at a relative humidity 75:
10 ppm
permissible so2 contaminant concentration at a relative humidity 75:
25 ppm
pollution degree 5:
2 per IEC 61131-2
power consumption 5 v system supply:
30 mA
power consumption typ:
200 mA (DALI/DSI)
power supply:
DALI/DSI: 18 V (external)
protection type:
IP20
relative humidity without condensation:
0.95
shock resistance:
15g per IEC 60068-2-27
strip length:
8 9 mm / 0.31 0.35 inch
supply voltage system:
5 VDC: via data contacts
surrounding air temperature operation:
0 55 C
surrounding air temperature storage:
-40 85 C
topology:
Number of slaves (DALI): 64: Number of slaves (DSI): 100