WAGO 788-306 relay module, 60 VDC, 16 A, SPDT, DIN rail mount
Wago
- Reinforced insulation between coil and contacts
- A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.
- To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.
The WAGO 788 series plug-in relay assembly features a single-pole (1P) design with a red LED indicator and operates on a control voltage of 54-66Vdc (60Vdc nominal). It includes a Single Pole Double Throw (SPDT) contact configuration and is electromechanical in nature. The relay supports a rated current of 16A continuously, 6A at 250Vac (AC-15), and 2A at 24Vdc (DC-13). It utilizes Push-in CAGE CLAMP connections for ease of installation and is designed for DIN-35 rail mounting with a 15mm width. The contacts are made from Silver-Nickel (AgNi 90/10) material, and the assembly is rated IP20 for protection. This relay is equivalent to the model 788306.
- bounce time typ:
- 6 ms
- color:
- Gray
- connection technology:
- Push-in CAGE CLAMP
- contact material relay:
- AgNi 90/10
- country of origin sales organisation germany:
- DE
- depth from upper edge of din rail:
- 54 mm / 2.126 inch
- dielectric strength control load circuit ac 1 min:
- 5 kVrms
- dielectric strength open contact ac 1 min:
- 1 kVrms
- drop out time typ:
- 6 ms
- electrical life no resistive load 23 c:
- 30 x 103 switching operations
- fine stranded conductor:
- 0.34 2.5 mm / 22 14 AWG
- fire load:
- 0.660 MJ
- height:
- 86 mm / 3.386 inch
- input voltage range:
- 10 %
- inrush current resistive max:
- (AC) 30 A / 4 s
- limiting continuous current:
- 16 A
- mechanical life:
- 30 x 106 switching operations
- mounting type:
- DIN-35 rail
- nominal input current at un:
- 11 mA
- nominal input voltage un:
- DC 60 V
- note:
- Reinforced insulation between coil and contactsTo protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.
- number of changeover switchover contacts:
- 1
- packaging type:
- Box
- pollution degree:
- 3
- processing temperature:
- -25 +50 C
- protection type:
- IP20
- pull in time typ:
- 8 ms
- rated surge voltage:
- 4 kV
- rated voltage:
- 250 V
- recommended minimum load:
- 12 V / 10 mA
- safety information 1:
- A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.
- solid conductor:
- 0.34 2.5 mm / 22 14 AWG
- standards specifications:
- EN 61010-2-201 || EN 61810-1 || EN 61373 || UL 508 (max. 10 A)
- status indicator:
- Red LED
- strip length:
- 9 10 mm / 0.35 0.39 inch
- surrounding air operating temperature for ul:
- -40 50 C
- surrounding air temperature operation at un:
- -40 70 C
- surrounding air temperature storage:
- -40 70 C
- switching capacity:
- AC-15: 6 A / AC 250 V: DC-13: 2 A / DC 24 V
- switching frequency with without load max:
- 6 min-1 / 1200 min-1
- switching power resistive max:
- AC 4000 VA: DC (see load limit curve)
- switching voltage max:
- AC 250 V
- wago basic relay:
- 788-162
- weight:
- 46.027 g
- width:
- 15 mm / 0.591 inch