Description
Relay socket with relay and status indicator; Compact terminal block, 3-pole, CCO; 230 VAC
View AllClose
- Reinforced insulation between coil and contacts
- A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.
- To prevent damaging the gold layer, 30 VDC switching voltages and 50 mA currents shall not be exceeded. Higher switching power evaporates the gold layer. The resulting deposits in the housing may reduce the service life.
- Inductive loads have to be attenuated by an appropriate protective circuit in order to protect relay coils and contacts.
The WAGO 788 series plug-in relay assembly features a single-pole, single-pole double throw (SPDT) contact with a control voltage range of 207-253Vac (230Vac nominal). It has an electromechanical design with a rated current of 50mA at 30Vdc (DC-13) and uses Push-in CAGE CLAMP connections. The relay is designed for DIN-35 rail mounting with a 15mm width and has an IP20 protection rating. The contacts are made of hard gold-plated silver-nickel (AgNi + Au) to prevent evaporation of the gold flash. It includes a red LED indicator and is equivalent to the 788608 model.