WAGO 788-608 relay module, 230 VAC, 16 A, SPDT, DIN rail mount
Wago
- Reinforced insulation between coil and contacts
- A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.
- To prevent damaging the gold layer, 30 VDC switching voltages and 50 mA currents shall not be exceeded. Higher switching power evaporates the gold layer. The resulting deposits in the housing may reduce the service life.
- Inductive loads have to be attenuated by an appropriate protective circuit in order to protect relay coils and contacts.
The WAGO 788 series plug-in relay assembly features a single-pole, single-pole double throw (SPDT) contact with a control voltage range of 207-253Vac (230Vac nominal). It has an electromechanical design with a rated current of 50mA at 30Vdc (DC-13) and uses Push-in CAGE CLAMP connections. The relay is designed for DIN-35 rail mounting with a 15mm width and has an IP20 protection rating. The contacts are made of hard gold-plated silver-nickel (AgNi + Au) to prevent evaporation of the gold flash. It includes a red LED indicator and is equivalent to the 788608 model.
- color:
- Gray
- connection technology:
- Push-in CAGE CLAMP
- contact material relay:
- AgNi + Au
- country of origin sales organisation germany:
- DE
- depth from upper edge of din rail:
- 54 mm / 2.126 inch
- dielectric strength control load circuit ac 1 min:
- 5 kVrms
- dielectric strength open contact ac 1 min:
- 1 kVrms
- drop out time typ:
- 3 ms
- electrical life no resistive load 23 c:
- 70 x 103 switching operations
- fine stranded conductor:
- 0.34 2.5 mm / 22 14 AWG
- fire load:
- 0.870 MJ
- height:
- 86 mm / 3.386 inch
- input voltage range:
- 10 %
- limiting continuous current:
- 16 A
- mechanical life:
- 30 x 106 switching operations
- mounting type:
- DIN-35 rail
- nominal input current at un:
- 5 mA
- nominal input voltage un:
- AC 230 V
- note:
- Reinforced insulation between coil and contactsTo prevent damaging the gold layer, 30 VDC switching voltages and 50 mA currents must not be exceeded. Higher switching power eventually evaporates the gold layer. The resulting deposits in the housing m
- number of changeover switchover contacts:
- 1
- packaging type:
- Box
- pollution degree:
- 3
- processing temperature:
- -25 +50 C
- protection type:
- IP20
- pull in time typ:
- 7 ms
- rated surge voltage:
- 4 kV
- rated voltage:
- 250 V
- recommended minimum load:
- 5 V / 2 mA / 50 mW
- safety information 1:
- A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.
- solid conductor:
- 0.34 2.5 mm / 22 14 AWG
- standards specifications:
- EN 61010-2-201 || EN 61810-1 || EN 61373 || UL 508
- status indicator:
- Red LED
- strip length:
- 9 10 mm / 0.35 0.39 inch
- surrounding air operating temperature for ul:
- -40 50 C
- surrounding air temperature operation at un:
- -40 70 C
- surrounding air temperature storage:
- -40 70 C
- switching capacity:
- AC-15: 6 A / AC 250 V: DC-13: 2 A / DC 24 V
- switching power resistive max:
- AC 4000 VA: DC (see load limit curve)
- switching voltage max:
- AC 250 V
- wago basic relay:
- 788-179
- weight:
- 47.847 g
- width:
- 15 mm / 0.591 inch