Description
SSR DC 24V
View AllClose
Technical Data
- Nominal input voltage U<sub>N</sub>: DC 24 V
- Input voltage range (low level): DC 0 3 V
- Input voltage range (high level): DC 10 30 V
- Nominal input current at U<sub>N</sub>: 11 mA
- Circuit type: 2-conductor termination
- Limiting continuous current: 5 A; 4.5 A (UL)
- Nominal output voltage: DC 24 V
- Output voltage range: DC 0 35 V
- Max. voltage drop at output: nbsp;DC 0.3 V
- Min. switching current: 1 mA
- Turn-on time: nbsp;50 s
- Drop-out time: nbsp;250 s
- Switching frequency: nbsp;3 kHz
- Status indication: LED green
- Rated voltage: 300 V
- Overvoltage category: II
- Pollution degree: 2
- Dielectric strength, control/load circuit (AC, 1 min): 3.51 kVrms
- Insulation type (control/load circuit): Reinforced insulation (safe isolation)
- Insulation type (adjacent devices): Reinforced insulation (safe isolation)
- Protection class: IP20
Connection Data
- Connection technology: Push-in CAGE CLAMP<sup></sup>
- Solid conductor: 0.34 2.5 mm / 22 14 AWG
- Fine-stranded conductor: 0.34 2.5 mm / 22 14 AWG
- Strip length: 9 10 mm / 0.35 0.39 inch
Geometrical Data
- Width: 15 mm / 0.591 inch
- Height from upper-edge of DIN-35 rail: 54 mm / 2.126 inch
- Depth: 86 mm / 3.386 inch
Mechanical Data
- Type of mounting: DIN-35 rail
Material Data
- Fire load: 0.000 MJ
- Weight: 41.600 g
Environmental Requirements
- Surrounding air (operating) temperature at U<sub>N</sub>: -25 70 C
- Surrounding air (storage) temperature: -40 85 C
- Processing temperature: -25 +50 C
- Surrounding air (operating) temperature for UL: -25 60 C
- Relative humidity: nbsp;95% (no condensation permissible)
- Max. operating altitude: 2000 m
Standards and specifications
- Standards/specifications: EN 61010-2-201; EN 61000-6-2; EN 61000-6-3; EN 61373
Elementary relay
- WAGO elementary relay: 788-754
Commercial data
- Packaging type: BOX
- Country of origin: DE
- GTIN: 4055143900058
- Customs Tariff No.: 85365005000