WAGO 855-3001/250-001 Split-Core Current Transformer, 250A Primary, 1A Secondary, 0.2 VA, 3m Cable
Wago| Description | Split-core current transformer; 250 A / 1 A; 3 m long | ||||||||||||||||||||||||||||||||||||||
| Remarks | Item description: Short description: WAGO's compact split-core current transformers are ideal for retrofit applications in existing systems. They are particularly suited for applications in which the current path may not be disrupted. The transformer's accuracy permits extremely precise current measurements. The split-core current transformers are capable of supplying the specified rated power at the end of the secondary cable. All transformers are supplied with color-coded cables. Two UV-resistant cable ties for reliable and easy mounting are also included. Features: | ||||||||||||||||||||||||||||||||||||||
| Item properties | Miscellaneous
| ||||||||||||||||||||||||||||||||||||||
The Split-core measurement current transformer (CT) from WAGO's 855 series, with a 250/1A ratio and Accuracy Class 1 (Cl.1), has a maximum burden of 0.2VA. It features a 3-meter cable with bare end flying leads, is designed for cable mounting, and has an IP20 protection rating. The CT is suitable for ambient temperatures ranging from -10°C to +55°C and is equivalent to model number 8553001250001.
- accuracy class:
- 1
- cable length:
- 3 m
- cable type:
- 2 x 0.5 mm: fine-stranded
- color code:
- Brown = S1: blue = S2
- conformity marking:
- CE
- country of origin sales organisation germany:
- NL
- feedthrough for measurement conductor:
- 18 mm
- fire load:
- 0.000 MJ
- flammability class per ul94:
- V2
- housing material:
- PA 66
- mounting type:
- Split-core current transformer (suspended)
- operating altitude max:
- 2000 m
- packaging type:
- Box
- primary rated current:
- 250 A
- rated continuous thermal current icth:
- 1
- rated frequency:
- 50 60 Hz
- rated power sr:
- 0.2 VA
- rated short time thermal current ith:
- 60 x IN / 1 s
- rated surge current idyn:
- 2.5 x Ith
- relative humidity:
- 5 85 % (without condensation)
- secondary rated current:
- 0.0416666666666667
- standards specifications:
- EN 61869-1 || EN 61869-2
- surrounding air temperature operation:
- -10 55 C
- surrounding air temperature storage:
- -20 70 C
- test voltage:
- AC 3 kV: 50 Hz: 1 min
- weight:
- 237.000 g