Synchronous Motor Control Profile:
permanent magnet motor || synchronous reluctance motor
Analogue Output Number:
2
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Depth:
203 mm
Rohs Exemption Information:
Yes
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
Enclosure Mounting:
wall mounted
Physical Interface:
Ethernet || 2-wire RS 485
Permissible Temporary Current Boost:
1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
Power Range:
4-6 kW 200-240 V 3 phase
Discrete Output Number:
0
Maximum Horse Power Rating:
5 hp normal duty || 4 hp heavy duty
Analogue Input Number:
3
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Standards:
UL 508C || IEC 61800-3 || IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
Communication Port Protocol:
Modbus TCP || Ethernet || Modbus serial
Asynchronous Motor Control Profile:
optimized torque mode || constant torque standard || variable torque standard
Discrete Input Logic:
16 preset speeds
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Variant:
standard version
Overvoltage Category:
III
Continuous Output Current:
18.7 A 4 kHz normal duty || 13.7 A 4 kHz heavy duty
Emc Filter:
without EMC filter
Number Of Addresses:
1-247 Modbus serial
Maximum Thdi:
<48 % full load IEC 61000-3-12
Vibration Resistance:
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Mounting Mode:
wall mount
Isolation:
between power and control terminals
Noise Level:
54.5 dB
Switching Frequency:
2...12 kHz adjustable || 4...12 kHz with derating factor
Speed Drive Output Frequency:
0.1-500 Hz
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
Device Short Name:
ATV630
[Us] Rated Supply Voltage:
200...240 V
Circularity Profile:
ENVEOLI1501005EN
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Operating Position:
vertical +/- 10 degree
Pollution Degree:
2
Ambient Air Temperature For Storage:
-40-70 °C
Option Card:
slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A c
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
Type Of Cooling:
forced convection
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Product Or Component Type:
variable speed drive
Product Destination:
asynchronous motors || synchronous motors
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Discrete And Process Manufacturing:
building - HVAC compressor centrifugal || food and beverage processing other application || mining mineral and metal fan || mining mineral and metal pump || oil and gas fan || water and waste water other application || building - HVAC screw compresso
Discrete Input Logic:
positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
Degree Of Protection:
UL type 1 UL 508C
Volume Of Cooling Air:
38 m3/h
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Net Weight:
4.6 kg
Sustainable Offer Status:
Green Premium product
Type Of Polarization:
no impedance
Data Format:
8 bits, configurable odd, even or no parity
Prospective Line Isc:
50 kA
Quantity Per Set:
1
Relay Output Number:
3
Environmental Disclosure:
ENVPEP1501005EN
Local Signalling:
for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
Output Voltage:
<= power supply voltage
Input Compatibility:
DI1...DI6 discrete input level 1 PLC IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
Transmission Frame:
RTU
Height:
350 mm
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Transmission Rate:
10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
China Rohs Regulation:
X
Braking To Standstill:
by DC injection
Mercury Free:
Yes
Nominal Switching Frequency:
4 kHz
Electrical Connection:
control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || motor screw terminal 6 mm² AWG 10 || line side screw terminal 4...6 mm² AWG 12...AWG10
Discrete Output Type:
relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V
Motor Slip Compensation:
can be suppressed || not available in permanent magnet motor law || automatic whatever the load || adjustable
Apparent Power:
5.4 kVA 240 V normal duty) || 4.2 kVA 240 V heavy duty)
Noise Level:
54.5 dB 86/188/EEC
Maximum Output Frequency:
500 kHz
Phase:
3 phase
Supply:
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
Width:
144 mm
Relay Output Type:
configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
Discrete Input Type:
DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
Safety Function:
STO (safe torque off) SIL 3
Product Specific Application:
process and utilities
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Supply Frequency:
50...60 Hz - 5...5 %
Discrete Input Number:
8
Frequency Resolution:
display unit 0.1 Hz || analog input 0.012/50 Hz
Method Of Access:
slave Modbus TCP
Ip Degree Of Protection:
IP21IEC 61800-5-1 || IP21IEC 60529
Ambient Air Temperature For Operation:
-15-50 °C without derating) || 50-60 °C with derating factor)
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Power Dissipation In W:
natural convection 38 W 200 V 4 kHz || forced convection 141 W 200 V 4 kHz
Connector Type:
RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
Range Of Product:
Altivar Process ATV600
Motor Power Kw:
4 kW normal duty) || 3 kW heavy duty)
Upgradeability:
Upgraded components available
[Us] Rated Supply Voltage:
200...240 V - 15...10 %
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Maximum Transient Current:
20.6 A 60 s normal duty) || 20.6 A 60 s heavy duty)
Pollution Degree:
2 IEC 61800-5-1
Product Certifications:
ATEX zone 2/22 || ATEX INERIS || TÜV || UL || CSA || DNV-GL
Regulation Loop:
adjustable PID regulator
Line Current:
15.1 A 200 V normal duty) || 12.9 A 240 V normal duty) || 11.7 A 200 V heavy duty) || 10.2 A 240 V heavy duty)
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Maximum Switching Current:
relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
Marking:
CE
Brochure:
View
Catalog:
View
Datasheet:
View
$2,203.69

Description

This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 200V to 240V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 4kW / 5hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 3kW / 4hp for applications requiring significant overload (up to 150%). It weighs 4.6kg and its dimensions are, 144mm wide, 350mm high, 203mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
View AllClose