Schneider Electric

Schneider Electric CAD326FD TeSys Deca control relay - 3 NO + 2 NC - <= 690 V - 110 V DC standard coil

(No reviews yet) Write a Review
SKU:
CAD326FD
MPN:
CAD326FD
Condition:
New
[Uc] Control Circuit Voltage:
110 V DC
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Net Weight:
0.58 kg
Utilisation Category:
AC-14 || AC-15 || DC-13
Inrush Power In W:
5.4-5.4 W 20°C)
Depth:
93 mm
Sustainable Offer Status:
Green Premium product
Device Short Name:
CAD
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
[Ue] Rated Operational Voltage:
<= 690 V AC 25...400 Hz
Mercury Free:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Maximum Operating Rate:
180 cyc/mn
Country of Origin:
Indonesia
Minimum Switching Current:
5 mA
Range:
TeSys || TeSys Deca
Mechanical Robustness:
shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
Operating Altitude:
0...9842.52 ft (0...3000 m)
Circularity Profile:
ENVEOLI1102030EN
Time Constant:
28 ms
Mechanical Durability:
30 Mcycles
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Minimum Switching Voltage:
17 V
Eu Rohs Directive:
Compliant with Exemptions
Mounting Support:
plate || rail
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Standards:
EN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1
Irms Rated Making Capacity:
140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
Weight:
0.58 kg
Ip Degree Of Protection:
IP2X front face VDE 0106
Associated Fuse Rating:
10 A gG conforming to IEC 60947-5-1
Rohs Exemption Information:
Yes
Operating Time:
53...72 ms coil energisation and NO closing || 16...24 ms coil de-energisation and NO opening || 47...63 ms coil energisation and NC opening || 15...25 ms coil de-energisation and NC closing
Product Or Component Type:
control relay
[Ui] Rated Insulation Voltage:
600 V UL || 600 V CSA || 690 V IEC 60947-5-1
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C)
Connections - Terminals:
lugs-ring terminals 8 mm)
Ambient Air Temperature For Storage:
-60-80°C
Non-Overlap Time:
1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
Environmental Disclosure:
ENVPEP110230EN
Insulation Resistance:
> 10 MOhm
Contactor Application:
control circuit
$112.20

Description

TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 110V DC control circuit with no inrush consumption and equipped with a surge suppression device, connection by lugs. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
View AllClose