Schneider Electric

Schneider Electric CAD326L7 TeSys Deca control relay - 3 NO + 2 NC - <= 690 V - 200 V AC standard coil

(No reviews yet) Write a Review
SKU:
CAD326L7
MPN:
CAD326L7
Condition:
New
Associated Fuse Rating:
10 A gG conforming to IEC 60947-5-1
Mercury Free:
Yes
Irms Rated Making Capacity:
140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
Mechanical Durability:
30 Mcycles
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Mechanical Robustness:
shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
California Proposition 65:
WARNING: Cancer - www.P65Warnings.ca.gov
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile:
ENVEOLI1501004
Pole Contact Composition:
3 NO + 2 NC
Minimum Switching Current:
5 mA
Warranty:
18 months
[Ue] Rated Operational Voltage:
<= 690 V AC 25...400 Hz
Height:
77 mm
Operating Altitude:
0...9842.52 ft (0...3000 m)
Mounting Support:
rail || plate
Hold-In Power Consumption In Va:
8-8 VA 50 Hz (at 20°C)
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Insulation Resistance:
> 10 MOhm
Minimum Switching Voltage:
17 V
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C)
Ambient Air Temperature For Storage:
-60-80°C
Range:
TeSys || TeSys Deca
Control Circuit Type:
AC 50/60 Hz
Weight:
0.58 kg
Device Short Name:
CAD
Non-Overlap Time:
1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
Sustainable Offer Status:
Green Premium product
Pvc Free:
Yes
Product Certifications:
CB || CCC || UL || CSA || EAC || CE || UKCA
[Uc] Control Circuit Voltage:
200 V AC 50/60 Hz
Standards:
EN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1
Connections - Terminals:
lugs-ring terminals 8 mm)
Utilisation Category:
DC-13 || AC-15 || AC-14
Environmental Disclosure:
ENVPEP1501004
Maximum Operating Rate:
180 cyc/mn
Protective Treatment:
TH IEC 60068
Rohs Exemption Information:
Yes
Country of Origin:
Indonesia
Ip Degree Of Protection:
IP2X front face VDE 0106
[Ui] Rated Insulation Voltage:
600 V UL || 600 V CSA || 690 V IEC 60947-5-1
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Net Weight:
0.58 kg
Eu Rohs Directive:
Compliant with Exemptions
Contactor Application:
control circuit
Operating Time:
12...22 ms coil energisation and NO closing || 4...12 ms coil de-energisation and NO opening || 4...19 ms coil energisation and NC opening || 6...17 ms coil de-energisation and NC closing
$63.25

Description

TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 200V AC control circuit with no inrush consumption and equipped with a surge suppression device, connection by lugs. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
View AllClose