Schneider Electric

Schneider Electric GV4P80S Motor circuit breaker, TeSys GV4, 3P, 80A, Icu 100kA, thermal magnetic, Everlink terminals

(No reviews yet) Write a Review
SKU:
GV4P80S
MPN:
GV4P80S
Condition:
New
Country of Origin:
Poland
Fire Resistance:
960°C IEC 60695-2-11
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Halogen Content Performance:
Halogen free plastic parts product
Net Weight:
1.6 kg
Power Dissipation Per Pole:
4.6 W
Phase Failure Sensitivity:
yes IEC 60947-4-1
Product Name:
TeSys GV4 || TeSys Deca
Weight:
1.6 kg
Product Certifications:
IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
Pollution Degree:
3
Eu Rohs Directive:
Compliant with Exemptions
Trip Unit Technology:
thermal-magnetic || electronic
Mercury Free:
Yes
Product Or Component Type:
motor circuit breaker
Tightening Torque:
9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Range Of Product:
TeSys GV4
Ambient Air Temperature For Storage:
-50-85°C
Environmental Disclosure:
ENVPEP1704004EN
Line Rated Current:
80 A
Standards:
CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
Device Application:
motor protection
Breaking Capacity:
120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 100 kA 208Y/120 V AC
Ip Degree Of Protection:
IP40 IEC 60529
Control Type:
rotary handle
Warranty:
18 months
Operating Altitude:
5000 m
Sustainable Offer Status:
Green Premium product
Suitability For Isolation:
yes IEC 60947-1
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Rated Duty:
continuous IEC 60947-4-1
Depth:
165 mm
Color:
Gray RAL 7016)
Maximum Operating Rate:
25 cyc/h
Climatic Withstand:
IACS E10
[Ith] Conventional Free Air Thermal Current:
115 A IEC 60947-4-1
Range:
TeSys Deca
Magnetic Tripping Current:
1360-1360 A
Pvc Free:
Yes
Mechanical Durability:
40000 cycles
Device Short Name:
GV4P
Ik Degree Of Protection:
IK07 IEC 62262
Rohs Exemption Information:
Yes
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Electrical Durability:
14000 cycles AC-3 440 V In/2 || 7000 cycles AC-3 440 V In
$945.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 80A/690V, for protection of 3-phase motors 22-37kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 100kA@400V, start-stop control by rotary handle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 40-80A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
View AllClose