Schneider Electric GV4PE07N Motor circuit breaker, TeSys GV4, 3P, 7A, Icu 50kA, thermal magnetic, Everlink terminals
Schneider Electric
$695.00
TeSys GV motor circuit breaker, 3 poles (3P), 7A/690V, for protection of 3-phase motors 1.5-3kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 2.9-7A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
- Environmental Disclosure:
- ENVPEP1704004EN
- Operating Position:
- any position
- Net Weight:
- 1.45 kg
- [Ui] Rated Insulation Voltage:
- 800 V AC 50/60 Hz IEC 60947-2
- Product Or Component Type:
- motor circuit breaker
- Breaking Capacity:
- 100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 65 kA 208Y/120 V AC 50/60 Hz UL 60947 || 65 kA 240 V AC 50/60 Hz
- Pollution Degree:
- 3
- Depth:
- 116 mm
- Trip Unit Technology:
- electronic || thermal-magnetic
- Color:
- Gray RAL 7016)
- Pvc Free:
- Yes
- Product Certifications:
- IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
- Weight:
- 1.45 kg
- Standards:
- CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
- Warranty:
- 18 months
- Connections - Terminals:
- EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
- Circularity Profile:
- ENVEOLI1704004EN
- Ambient Air Temperature For Operation:
- -25-70°C
- Rated Duty:
- continuous IEC 60947-4-1
- Mechanical Durability:
- 40000 cycles
- Utilisation Category:
- category A IEC 60947-2 || AC-3 IEC 60947-4-1
- Suitability For Isolation:
- yes IEC 60947-1
- Fire Resistance:
- 960°C IEC 60695-2-11
- Phase Failure Sensitivity:
- yes IEC 60947-4-1
- Ik Degree Of Protection:
- IK07 IEC 62262
- Range Of Product:
- TeSys GV4
- Width:
- 81 mm
- [Ith] Conventional Free Air Thermal Current:
- 115 A IEC 60947-4-1
- Climatic Withstand:
- IACS E10
- Tightening Torque:
- 9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
- Line Rated Current:
- 0.291666666666667
- Poles Description:
- 3P
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Operating Altitude:
- 5000 m
- Mercury Free:
- Yes
- Ip Degree Of Protection:
- IP40 IEC 60529
- Halogen Content Performance:
- Halogen free plastic parts product
- Country of Origin:
- Poland
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-2
- Control Type:
- toggle
- Ambient Air Temperature For Storage:
- -50-85°C
- Electrical Durability:
- 40000 cycles AC-3 440 V In/2 || 40000 cycles AC-3 440 V In
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Motor Power Kw:
- 1.5-1.5 kW 400...415 V AC 50/60 Hz || 2.2-2.2 kW 400...415 V AC 50/60 Hz || 2.5-2.5 kW 400...415 V AC 50/60 Hz || 3-3 kW 400...415 V AC 50/60 Hz || 2.2-2.2 kW 500 V AC 50/60 Hz || 2.5-2.5 kW 500 V AC 50/60 Hz || 3-3 kW 500 V AC 50/60 Hz || 4-4 kW 500
- Power Dissipation Per Pole:
- 4.6 W
- Device Short Name:
- GV4PE
- Product Name:
- TeSys GV4 || TeSys Deca
- Magnetic Tripping Current:
- 119-119 A