- Depth:
- 86 mm
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Color:
- Black
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Continuous Current Rating:
- 0.8
- Device Application:
- distribution
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mercury Free:
- Yes
- Width:
- 104 mm
- Environmental Disclosure:
- ENVPEP2206028EN
- Pvc Free:
- Yes
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Network Frequency:
- 50/60 Hz
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Poles Description:
- 3P
- Circuit Breaker Application:
- HACR rated
- Product Certifications:
- UL || CSA || NOM
- Wire Stripping Length:
- 16 mm
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Rohs Exemption Information:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Trip Unit Name:
- MicroLogic 3.2
- Breaking Capacity Code:
- J
- Sustainable Offer Status:
- Green Premium product
- Pollution Degree:
- 3 IEC 60947-1
- Net Weight:
- 2.2 kg
- Circularity Profile:
- ENVEOLI2206028EN
- Height:
- 163 mm
- Control Type:
- toggle
- Terminal Identifier:
- AL150HD
- Range:
- PowerPact
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mounting Support:
- lug
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Product Or Component Type:
- circuit breaker
- Quality Labels:
- CE
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Warranty:
- 18 months
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Electrical Connection:
- lugs, line || lugs, load
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Communication Interface:
- Modbus || Ethernet
- Quantity Per Set:
- 1
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Utilisation Category:
- category A
- Line Rated Current:
- 100-100 A
- Suitability For Isolation:
- yes IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Mounting Mode:
- unit mount lug)
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Product Name:
- PowerPact H
- Protected Poles Description:
- 3t
- Eu Rohs Directive:
- Compliant with Exemptions