- Quantity Per Set:
- 1
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Control Type:
- toggle
- Environmental Disclosure:
- ENVPEP2206028EN
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70°C
- Product Or Component Type:
- circuit breaker
- Line Rated Current:
- 100-100 A
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Weight:
- 2.2 kg
- Network Frequency:
- 50/60 Hz
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.2 A, LSIG
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Depth:
- 86 mm
- Local Signaling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Breaking Capacity Code:
- L
- Eu Rohs Directive:
- Compliant with Exemptions
- Suitability For Isolation:
- yes IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Poles Description:
- 3P
- Protected Poles Description:
- 3t
- Terminal Identifier:
- AL150HD
- Wire Stripping Length:
- 16 mm
- Circuit Breaker Application:
- HACR rated
- Warranty:
- 18 months
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Device Application:
- distribution
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Length:
- 16 mm
- Country of Origin:
- United States
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Height:
- 163 mm
- Continuous Current Rating:
- 0.8
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Circularity Profile:
- ENVEOLI2206028EN
- Range:
- PowerPact
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Electrical Connection:
- lugs, line || lugs, load
- Width:
- 104 mm
- Sustainable Offer Status:
- Green Premium product
- Pvc Free:
- Yes
- Utilisation Category:
- category A
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Quality Labels:
- CE
- Trip Unit Name:
- MicroLogic 6.2 A