- Terminal Identifier:
- AL150HD
- Mounting Mode:
- unit mount lug)
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Warranty:
- 18 months
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Eu Rohs Directive:
- Compliant with Exemptions
- Mounting Support:
- lug
- Wire Stripping Length:
- 16 mm
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Range:
- PowerPact
- Magnetic Hold Current:
- 350 A
- Pollution Degree:
- 3 IEC 60947-1
- Depth:
- 86 mm
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Utilisation Category:
- category A
- Magnetic Tripping Current:
- 750-750 A
- Trip Unit Technology:
- thermal-magnetic
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Line Rated Current:
- 15-15 A
- Product Or Component Type:
- circuit breaker
- Network Frequency:
- 50/60 Hz
- Length:
- 16 mm
- Height:
- 163 mm
- Continuous Current Rating:
- 0.8
- Product Certifications:
- UL || CSA || NOM
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Product Name:
- PowerPact H
- Ambient Air Temperature For Storage:
- -50-85°C
- Electrical Connection:
- terminal nut, line || lugs, load
- Weight:
- 2.2 kg
- Mercury Free:
- Yes
- Circuit Breaker Application:
- HACR rated
- Color:
- Black
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Quality Labels:
- CE
- Country of Origin:
- United States
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Quantity Per Set:
- 1
- Communication Interface:
- Modbus || Ethernet
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Local Signaling:
- switched off (OFF) 1 trip indicator green)
- Protected Poles Description:
- 3t
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Breaking Capacity Code:
- L
- Control Type:
- toggle
- Device Application:
- distribution
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information