- Control Type:
- toggle
- Continuous Current Rating:
- 0.8
- Ambient Air Temperature For Storage:
- -50-85°C
- Net Weight:
- 2.2 kg
- Protected Poles Description:
- 3t
- [Ics] Rated Service Breaking Capacity:
- 150 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 125 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 75 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 690 V AC 50/60 Hz IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Magnetic Hold Current:
- 800 A
- Pollution Degree:
- 3 IEC 60947-1
- Magnetic Tripping Current:
- 1450-1450 A
- Environmental Disclosure:
- ENVPEP2206028EN
- Poles Description:
- 3P
- Ambient Air Temperature For Operation:
- -25-70°C
- Circuit Breaker Application:
- HACR rated
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Breaking Capacity Code:
- R
- Device Application:
- distribution
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Range:
- PowerPact
- Network Frequency:
- 50/60 Hz
- Mounting Support:
- lug
- Breaking Capacity:
- 200 kA 240 V AC 50/60 Hz UL 489 || 200 kA 480 V AC 50/60 Hz UL 489 || 100 kA 600 V AC 50/60 Hz UL 489
- Length:
- 16 mm
- Mercury Free:
- Yes
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Trip Unit Name:
- MicroLogic 3.2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Circularity Profile:
- ENVEOLI2206028EN
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Quality Labels:
- CE
- Rohs Exemption Information:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mounting Mode:
- unit mount lug)
- Wire Stripping Length:
- 16 mm
- Local Signaling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Utilisation Category:
- category A
- Electrical Connection:
- terminal nut, line || lugs, load
- Terminal Identifier:
- AL150HD
- Product Name:
- PowerPact H
- Weight:
- 2.2 kg
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Pvc Free:
- Yes
- Product Certifications:
- UL || CSA || NOM
- Depth:
- 86 mm
- Suitability For Isolation:
- yes IEC 60947-2
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal