- Protection Type:
- overload protection || short-circuit protection
- Ip Degree Of Protection:
- front cover IP40
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Wire Stripping Length:
- 25 mm
- Suitability For Isolation:
- yes IEC 60947-2
- Net Weight:
- 2.4 kg
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Ambient Air Temperature For Storage:
- -50-85 °C
- Rohs Exemption Information:
- Yes
- Poles Description:
- 3P
- Sustainable Offer Status:
- Green Premium product
- Mounting Mode:
- unit mount lug)
- Electrical Connection:
- lugs, line || lugs, load
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Product Or Component Type:
- circuit breaker
- Pvc Free:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- Continuous Current Rating:
- 0.8
- Line Rated Current:
- 250-250 A
- Width:
- 104 mm
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2 S, LSI
- Utilisation Category:
- category A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206032EN
- Quality Labels:
- CE
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mercury Free:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Depth:
- 86 mm
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Circularity Profile:
- ENVEOLI2206032EN
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Product Certifications:
- UL || CSA || NOM
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Trip Unit Name:
- MicroLogic 3.2 S
- Pollution Degree:
- 3
- Control Type:
- toggle
- Breaking Capacity Code:
- J
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Height:
- 191 mm
- Warranty:
- 18 months
- Communication Interface:
- Modbus
- Terminal Identifier:
- AL250JD
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Mounting Support:
- lug
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Network Frequency:
- 50/60 Hz