- Product Or Component Type:
- circuit breaker
- Control Type:
- toggle
- Local Signaling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Eu Rohs Directive:
- Compliant with Exemptions
- Product Certifications:
- UL || CSA || NOM
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Trip Unit Name:
- MicroLogic 5.2 A
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Ambient Air Temperature For Storage:
- -50-85°C
- Mounting Mode:
- unit mount lug)
- Warranty:
- 18 months
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Mercury Free:
- Yes
- Terminal Identifier:
- AL250JD
- Ip Degree Of Protection:
- front cover IP40
- Circuit Breaker Application:
- HACR rated
- Continuous Current Rating:
- 0.8
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Rohs Exemption Information:
- Yes
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Protection Type:
- overload protection || short-circuit protection
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 5.2 A, LSI
- Circularity Profile:
- ENVEOLI2206032EN
- Weight:
- 2.4 kg
- Poles Description:
- 3P
- Wire Stripping Length:
- 25 mm
- Network Frequency:
- 50/60 Hz
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Pvc Free:
- Yes
- Quality Labels:
- CE
- Communication Interface:
- Modbus
- Length:
- 25 mm
- Pollution Degree:
- 3
- Country of Origin:
- United States
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Ambient Air Temperature For Operation:
- -25-70°C
- Depth:
- 86 mm
- Environmental Disclosure:
- ENVPEP2206032EN
- Utilisation Category:
- category A
- Line Rated Current:
- 250-250 A
- Net Weight:
- 2.4 kg