Schneider Electric

Schneider Electric JRL36200 Circuit breaker, PowerPacT J, 200A, 3 pole, 600VAC, 100kA, lugs, thermal magnetic, 80%

(No reviews yet) Write a Review
SKU:
JRL36200
MPN:
JRL36200
Condition:
New
Awg Gauge:
AWG 3/0...350 kcmil aluminium/copper terminals
Breaking Capacity Code:
R
Trip Unit Technology:
thermal-magnetic
Mounting Mode:
unit mount lug)
Quality Labels:
CE
Length:
25 mm
Country of Origin:
United States
Product Or Component Type:
circuit breaker
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Magnetic Tripping Current:
2000-2000 A
Depth:
86 mm
Tightening Torque:
25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
[Ics] Rated Service Breaking Capacity:
150 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 125 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 75 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 690 V AC 50/60 Hz IEC 60947-2
Communication Interface:
Modbus
Sustainable Offer Status:
Green Premium product
Continuous Current Rating:
0.8
Width:
104 mm
Ambient Air Temperature For Operation:
-25-70°C
Poles Description:
3P
Circuit Breaker Application:
HACR rated
Pollution Degree:
3
Net Weight:
2.4 kg
Electrical Connection:
lugs, line || lugs, load
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Wire Stripping Length:
25 mm
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Protection Type:
overload protection || short-circuit protection
Suitability For Isolation:
yes IEC 60947-2
Pvc Free:
Yes
Magnetic Hold Current:
1000 A
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Ip Degree Of Protection:
front cover IP40
Circularity Profile:
ENVEOLI2206031EN
Local Signaling:
switched off (OFF) 1 trip indicator green)
Eu Rohs Directive:
Compliant with Exemptions
Line Rated Current:
200-200 A
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Mercury Free:
Yes
Terminal Identifier:
AL250JD
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Ambient Air Temperature For Storage:
-50-85°C
Weight:
2.4 kg
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Network Frequency:
50/60 Hz
Control Type:
toggle
Breaking Capacity:
200 kA 240 V AC 50/60 Hz UL 489 || 200 kA 480 V AC 50/60 Hz UL 489 || 100 kA 600 V AC 50/60 Hz UL 489
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
$9,212.00

Description

PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 100kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 200A, 3 pole, circuit breaker has a breaking capacity of 100kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose