Schneider Electric

Schneider Electric LC1D115SD IEC contactor, TeSys Deca, nonreversing, 115A, 75HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 72VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D115SD
MPN:
LC1D115SD
Condition:
New
Hold-In Power Consumption In W:
2.4-5.1 W 20°C
Eu Rohs Directive:
Compliant with Exemptions
Product Certifications:
UL || CSA || CCC || UKCA || CE || EAC || Marine
Depth:
136 mm
[Icw] Rated Short-Time Withstand Current:
250 A 40°C - 10 min for power circuit || 550 A 40°C - 1 min for power circuit || 950 A 40°C - 10 s for power circuit || 1100 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Mechanical Durability:
8 Mcycles
Contactor Application:
resistive load || motor control
Signaling Circuit Frequency:
25...400 Hz
Maximum Operating Rate:
1200 cyc/h 60°C
[Ue] Rated Operational Voltage:
power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
Pole Contact Composition:
3 NO
Device Short Name:
LC1D
Overvoltage Category:
III
Warranty:
18 months
Sustainable Offer Status:
Green Premium product
Protective Cover:
with
Control Circuit Type:
DC standard
Fire Resistance:
850°C IEC 60695-2-1
Protective Treatment:
THIEC 60068-2-30
Ip Degree Of Protection:
IP20 front face IEC 60529
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Country of Origin:
Czechia
Control Circuit Voltage Limits:
0.75...1.2 Uc -40-55°C operational DC || 0.15...0.4 Uc -40-70°C drop-out DC || 1...1.2 Uc 55-70°C operational DC
Insulation Resistance:
> 10 MOhm for Signaling circuit
Minimum Switching Current:
5 mA for Signaling circuit
Associated Fuse Rating:
250 A gG at <= 690 V coordination type 1 for power circuit || 200 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Circularity Profile:
ENVEOLI100405EN
Power Dissipation Per Pole:
24 W AC-1 || 7.9 W AC-3 || 7.9 W AC-3e
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Utilisation Category:
AC-1 || AC-4 || AC-3 || AC-3e
[Ith] Conventional Free Air Thermal Current:
200 A (at 60°C) for power circuit
Coil Technology:
with integral suppression device
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Product Or Component Type:
contactor
Operating Time:
20...35 ms closing || 40...75 ms opening
Electrical Durability:
0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² -
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Height:
158 mm
Sustainable Packaging:
Yes
Net Weight:
2.5 kg
Mounting Support:
rail || plate
Mercury Free:
Yes
Operating Altitude:
0...9842.52 ft (0...3000 m)
Maximum Horse Power Rating:
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 40 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 75 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Irms Rated Making Capacity:
1260 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
$479.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with a 600VAC up to 250A circuit breaker, this contactor can have a SCCR up to 50kA. When used with 600VAC Class J or CC fuses up to 250A, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 72 VDC coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose