Schneider Electric

Schneider Electric LC1D188ED IEC contactor, TeSys Deca, nonreversing, 32A resistive, 4 pole, 2 NO and 2 NC, 48VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D188ED
MPN:
LC1D188ED
Condition:
New
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Operating Altitude:
0...9842.52 ft (0...3000 m)
Rohs Exemption Information:
Yes
Pollution Degree:
3
Power Dissipation Per Pole:
2.5 W AC-1
Rated Breaking Capacity:
300 A at 440 V for power circuit conforming to IEC 60947
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Weight:
0.585 kg
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 32 A (at 60°C) for power circuit
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Maximum Operating Rate:
3600 cyc/h 60°C
Overvoltage Category:
III
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
[Icw] Rated Short-Time Withstand Current:
145 A 40°C - 10 s for power circuit || 240 A 40°C - 1 s for power circuit || 40 A 40°C - 10 min for power circuit || 84 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Warranty:
18 months
Environmental Disclosure:
ENVPEP110230EN
Protective Cover:
with
Compatibility Code:
LC1D
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Minimum Switching Current:
5 mA for Signaling circuit
Operating Time:
63±15 % ms closing || 20±20 % ms opening
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947
Device Short Name:
LC1D
Electrical Durability:
1 Mcycles 32 A AC-1 <= 440 V
Range Of Product:
TeSys Deca
Mercury Free:
Yes
Signaling Circuit Frequency:
25...400 Hz
Depth:
107 mm
Protective Treatment:
THIEC 60068-2-30
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Average Impedance:
2.5 mOhm - Ith 32 A 50 Hz for power circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Inrush Power In W:
5.4-5.4 W 20°C)
Flame Retardance:
V1 conforming to UL 94
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Height:
91 mm
Country of Origin:
Indonesia
Product Certifications:
UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Circularity Profile:
ENVEOLI1102030EN
Width:
45 mm
Sustainable Offer Status:
Green Premium product
Eu Rohs Directive:
Compliant with Exemptions
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Poles Description:
4P
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
Mechanical Durability:
30 Mcycles
$200.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 32A resistive load rating. Contactor is supplied with a 48 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 4.21 inches deep. It weighs 1.29 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose