Schneider Electric LC1D386SLS207 IEC contactor, TeSys D, nonreversing, 38A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, low consumption 72VDC coil, open style
Schneider Electric
$303.72
This TeSys D contactor has been designed for motor control in railway applications. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a low consumption 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Minimum Switching Current:
- 5 mA for Signaling circuit
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
- Rated Breaking Capacity:
- 550 A at 440 V for power circuit conforming to IEC 60947
- Pole Contact Composition:
- 3 NO
- Eu Rohs Directive:
- Compliant with Exemptions
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
- Pvc Free:
- Yes
- Mechanical Durability:
- 30 Mcycles
- Average Impedance:
- 2 mOhm - Ith 50 A 50 Hz for power circuit
- Ambient Air Temperature For Storage:
- -60-80°C
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || EN 45545: R22 HL3 || EN 45545: R26 HL3 || DIN 5510-2
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Time Constant:
- 37 ms
- Device Short Name:
- LC1D
- Fire Resistance:
- 850°C IEC 60695-2-1
- Hold-In Power Consumption In W:
- 4-4 W 20°C
- Circularity Profile:
- N/A
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Utilisation Category:
- AC-1 || AC-3 || AC-4 || AC-3e
- Product Or Component Type:
- contactor
- Rohs Exemption Information:
- Yes
- Compatibility Code:
- LC1D
- Mercury Free:
- Yes
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Mounting Support:
- plate || rail
- Weight:
- 0.38 kg
- Net Weight:
- 0.38 kg
- Inrush Power In W:
- 4-4 W 20°C)
- Motor Power Kw:
- 9 kW at 220/230 V AC 50 Hz (AC-3) || 18.5 kW at 380/400 V AC 50 Hz (AC-3) || 18.5 kW at 415 V AC 50 Hz (AC-3) || 18.5 kW at 440 V AC 50 Hz (AC-3) || 18.5 kW at 500 V AC 50 Hz (AC-3) || 18.5 kW at 660/690 V AC 50 Hz (AC-3) || 9 kW at 220/230 V AC 50 H
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Range:
- TeSys || TeSys Deca
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Sustainable Offer Status:
- Green Premium product
- Height:
- 85 mm
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
- Power Dissipation Per Pole:
- 5 W AC-1 || 3 W AC-3 || 3 W AC-3e
- Overvoltage Category:
- III
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Operating Time:
- 77±15 % ms closing || 25±20 % ms opening
- Range Of Product:
- TeSys Deca
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Electrical Durability:
- 1.4 Mcycles 50 A AC-1 <= 440 V || 1.4 Mcycles 38 A AC-3 <= 440 V || 1.4 Mcycles 38 A AC-3e <= 440 V
- Maximum Operating Rate:
- 3600 cyc/h 60°C