Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || power circuit 5 N.m screw clamp terminals 1-25 mm² hex
Protective Treatment:
THIEC 60068-2-30
Mounting Support:
plate || rail
Irms Rated Making Capacity:
800 A at 440 V for power circuit conforming to IEC 60947
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Mercury Free:
Yes
Pollution Degree:
3
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-55°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-55°C operational AC 50 Hz || 0.85...1.1 Uc -40-55°C operational AC 60 Hz
Rohs Exemption Information:
Yes
Operating Altitude:
0...9842.52 ft (0...3000 m)
[Ue] Rated Operational Voltage:
power circuit <= 1000 V AC 25...400 Hz
Poles Description:
4P
Depth:
125 mm
Mechanical Durability:
6 Mcycles
Reach Free Of Svhc:
Yes
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Ip Degree Of Protection:
IP20 front face IEC 60529
Device Short Name:
LC1D
[Ie] Rated Operational Current:
60 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Eu Rohs Directive:
Compliant
Power Dissipation Per Pole:
5.4 W AC-1
Contactor Application:
resistive load
Electrical Durability:
1.4 Mcycles 60 A AC-1 <= 440 V
Warranty:
18 months
Country of Origin:
Czechia
Width:
85 mm
Weight:
1.44 kg
Fire Resistance:
850°C IEC 60695-2-1
Range Of Product:
TeSys Deca
Compatibility Code:
LC1D
Sustainable Offer Status:
Green Premium product
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Control Circuit Type:
AC 50/60 Hz
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Associated Fuse Rating:
80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Climatic Withstand:
IACS E10 exposure to damp heat
Average Impedance:
1.5 mOhm - Ith 60 A 50 Hz for power circuit
[Icw] Rated Short-Time Withstand Current:
320 A 40°C - 10 s for power circuit || 720 A 40°C - 1 s for power circuit || 72 A 40°C - 10 min for power circuit || 165 A 40°C - 1 min for power circuit
Inrush Power In Va:
245-245 VA 60 Hz cos phi 0.75 (at 20°C) || 245-245 VA 50 Hz cos phi 0.75 (at 20°C)
Product Or Component Type:
contactor
Rated Breaking Capacity:
800 A at 440 V for power circuit conforming to IEC 60947
Product Certifications:
UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
[Ith] Conventional Free Air Thermal Current:
60 A (at 60°C) for power circuit
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Maximum Operating Rate:
3600 cyc/h 60°C
$496.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 60A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 4.92 inches deep. It weighs 3.17 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.