Schneider Electric

Schneider Electric LC1D50ACD IEC contactor, TeSys Deca, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 36VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D50ACD
MPN:
LC1D50ACD
Condition:
New
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Overvoltage Category:
III
Protective Cover:
with
Inrush Power In W:
19-19 W 20°C)
Maximum Horse Power Rating:
3 hp at 115 V AC 50/60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 15 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 15 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 40 hp at 460/480 V AC 50/60 Hz for 3 phase
Electrical Durability:
1.45 Mcycles 50 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 50 A AC-3e <= 440 V
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Sustainable Offer Status:
Green Premium product
Ip Degree Of Protection:
IP20 front face IEC 60529
Control Circuit Voltage Limits:
0.1...0.3 Uc -40-70°C drop-out DC || 0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Operating Time:
50±15 % ms closing || 16...24 ms opening
Motor Power Kw:
15 kW at 220...230 V AC 50/60 Hz (AC-3) || 22 kW at 380...400 V AC 50/60 Hz (AC-3) || 30 kW at 500 V AC 50/60 Hz (AC-3) || 33 kW at 660...690 V AC 50/60 Hz (AC-3) || 25 kW at 415 V AC 50/60 Hz (AC-3) || 30 kW at 440 V AC 50/60 Hz (AC-3) || 11 kW at 4
Minimum Switching Voltage:
17 V for Signaling circuit
Sustainable Packaging:
Yes
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Range Of Product:
TeSys Deca
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Rated Breaking Capacity:
900 A at 440 V for power circuit conforming to IEC 60947
Hold-In Power Consumption In W:
7.4-7.4 W 20°C
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Operating Altitude:
0...9842.52 ft (0...3000 m)
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
Weight:
0.93 kg
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Mounting Support:
rail || plate
Contactor Application:
resistive load || motor control
Mechanical Durability:
10 Mcycles
Depth:
120 mm
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Pole Contact Composition:
3 NO
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Flame Retardance:
V1 conforming to UL 94
Power Dissipation Per Pole:
3.7 W AC-3 || 9.6 W AC-1 || 3.7 W AC-3e
Time Constant:
34 ms
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Signaling Circuit Frequency:
25...400 Hz
Fire Resistance:
850°C IEC 60695-2-1
Range:
TeSys || TeSys Deca
Maximum Operating Rate:
3600 cyc/h 60°C
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Pollution Degree:
3
Tightening Torque:
control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
$306.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 36 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose