Schneider Electric

Schneider Electric LC1D50AT7 IEC contactor, TeSys Deca, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 480VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D50AT7
MPN:
LC1D50AT7
Condition:
New
Ip Degree Of Protection:
IP20 front face IEC 60529
Fire Resistance:
850°C IEC 60695-2-1
Auxiliary Contact Composition:
1 NO + 1 NC
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
Minimum Switching Current:
5 mA for Signaling circuit
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Inrush Power In Va:
140-140 VA 60 Hz cos phi 0.75 (at 20°C)
Average Impedance:
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Insulation Resistance:
> 10 MOhm for Signaling circuit
Eu Rohs Directive:
Compliant
Maximum Operating Rate:
3600 cyc/h 60°C
Operating Time:
4...19 ms opening || 12...26 ms closing
Electrical Durability:
1.45 Mcycles 50 A AC-3 <= 440 V || 1.1 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 50 A AC-3e <= 440 V
Contactor Application:
resistive load || motor control
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Weight:
0.855 kg
Range:
TeSys || TeSys Deca
Protective Cover:
with
Protective Treatment:
THIEC 60068-2-30
Heat Dissipation:
4-5 W at 60 Hz
Operating Altitude:
0...9842.52 ft (0...3000 m)
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pvc Free:
Yes
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Minimum Switching Voltage:
17 V for Signaling circuit
Pole Contact Composition:
3 NO
Reach Free Of Svhc:
Yes
Product Or Component Type:
contactor
Motor Power Kw:
15 kW at 220...230 V AC 50/60 Hz (AC-3) || 22 kW at 380...400 V AC 50/60 Hz (AC-3) || 30 kW at 500 V AC 50/60 Hz (AC-3) || 33 kW at 660...690 V AC 50/60 Hz (AC-3) || 25 kW at 415 V AC 50/60 Hz (AC-3) || 30 kW at 440 V AC 50/60 Hz (AC-3) || 11 kW at 4
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Sustainable Packaging:
Yes
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 900 A at 440 V for power circuit conforming to IEC 60947
Compatibility Code:
LC1D
Rohs Exemption Information:
Yes
Environmental Disclosure:
ENVPEP1503009EN
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 60 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 60 Hz
Rated Breaking Capacity:
900 A at 440 V for power circuit conforming to IEC 60947
Power Dissipation Per Pole:
3.7 W AC-3 || 9.6 W AC-1 || 3.7 W AC-3e
Pollution Degree:
3
Overvoltage Category:
III
Mercury Free:
Yes
[Icw] Rated Short-Time Withstand Current:
400 A 40°C - 10 s for power circuit || 810 A 40°C - 1 s for power circuit || 84 A 40°C - 10 min for power circuit || 208 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Flame Retardance:
V1 conforming to UL 94
Maximum Horse Power Rating:
3 hp at 115 V AC 50/60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 15 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 15 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 40 hp at 460/480 V AC 50/60 Hz for 3 phase
Sustainable Offer Status:
Green Premium product
$295.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 480 VAC 60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.