Schneider Electric LC1D65A6FD IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 110VDC coil, open style
Schneider Electric
$403.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- Overvoltage Category:
- III
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Environmental Disclosure:
- ENVPEP1503009EN
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Country of Origin:
- France
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Protective Treatment:
- THIEC 60068-2-30
- Range Of Product:
- TeSys Deca
- Time Constant:
- 34 ms
- Pole Contact Composition:
- 3 NO
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
- Mechanical Durability:
- 10 Mcycles
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Minimum Switching Current:
- 5 mA for Signaling circuit
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Control Circuit Voltage Limits:
- 0.1...0.3 Uc -40-70°C drop-out DC || 0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- Operating Time:
- 50±15 % ms closing || 16...24 ms opening
- Rohs Exemption Information:
- Yes
- Motor Power Kw:
- 11 kW at 400 V AC 50/60 Hz (AC-4) || 18.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 30 kW at 380...400 V AC 50/60 Hz (AC-3) || 37 kW at 500 V AC 50/60 Hz (AC-3) || 37 kW at 660...690 V AC 50/60 Hz (AC-3) || 18.5 kW at 220...230 V AC 50/60 Hz (AC-3e) ||
- Product Certifications:
- CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Electrical Durability:
- 0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V || 1.45 Mcycles 65 A AC-3e <= 440 V
- Pollution Degree:
- 3
- Rated Breaking Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Poles Description:
- 3P
- Protective Cover:
- with
- Mercury Free:
- Yes
- Width:
- 55 mm
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- Weight:
- 0.935 kg
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Standards:
- EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
- [Icw] Rated Short-Time Withstand Current:
- 640 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
- Contactor Application:
- resistive load || motor control
- Mounting Support:
- rail || plate
- Depth:
- 120 mm
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Net Weight:
- 0.935 kg
- [Uc] Control Circuit Voltage:
- 110 V DC
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Flame Retardance:
- V1 conforming to UL 94