Schneider Electric LC1DT80AP7 IEC contactor, TeSys Deca, nonreversing, 80A resistive, 4 pole, 4 NO, 230VAC 50/60Hz coil, open style
Schneider Electric
$540.96
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 80A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.54 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Flame Retardance:
- V1 conforming to UL 94
- Sustainable Offer Status:
- Green Premium product
- Signaling Circuit Frequency:
- 25...400 Hz
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Mechanical Durability:
- 6 Mcycles
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Poles Description:
- 4P
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Toxic Heavy Metal Free:
- Yes
- Utilisation Category:
- AC-1
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Rohs Exemption Information:
- Yes
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Reach Free Of Svhc:
- Yes
- Mounting Support:
- rail || plate
- Operating Time:
- 4...19 ms opening || 12...26 ms closing
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Eu Rohs Directive:
- Compliant
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Protective Treatment:
- THIEC 60068-2-30
- Circularity Profile:
- ENVEOLI1503009EN
- Product Certifications:
- DNV || GL || UL || CSA || BV || GOST || CCC || LROS (Lloyds register of shipping) || RINA
- Coil Technology:
- without built-in suppressor module
- Rated Breaking Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Compatibility Code:
- LC1D
- Mercury Free:
- Yes
- Net Weight:
- 1.15 kg
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Fire Resistance:
- 850°C IEC 60695-2-1
- Heat Dissipation:
- 4-5 W at 50/60 Hz
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Control Circuit Type:
- AC 50/60 Hz
- Warranty:
- 18 months
- Depth:
- 120 mm
- Electrical Durability:
- 1.4 Mcycles 80 A AC-1 <= 440 V
- Protective Cover:
- with
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Pvc Free:
- Yes
- Pole Contact Composition:
- 4 NO
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || power circuit 5 N.m screw clamp terminals 1-25 mm² hex
- Ip Degree Of Protection:
- IP20 front face IEC 60529