- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Weight:
- 0.697 kg
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- Motor Power Kw:
- 3 kW at 220...230 V AC 50 Hz || 5.5 kW at 380...400 V AC 50 Hz || 5.5 kW at 415 V AC 50 Hz || 5.5 kW at 440 V AC 50 Hz || 7.5 kW at 500 V AC 50 Hz || 7.5 kW at 660...690 V AC 50 Hz
- Power Dissipation Per Pole:
- 1.56 W AC-1 || 0.36 W AC-3 || 0.36 W AC-3e
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Fire Resistance:
- 850°C IEC 60695-2-1
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Connections - Terminals:
- power circuit Faston terminals 2 || control circuit Faston terminals 1
- Product Name:
- TeSys Deca
- Flame Retardance:
- V1 conforming to UL 94
- Mechanical Durability:
- 15 Mcycles
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Eu Rohs Directive:
- Compliant
- Environmental Disclosure:
- ENVPEP1501004
- Heat Dissipation:
- 2-3 W 50/60 Hz
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Mounting Support:
- plate || rail
- Width:
- 90 mm
- [Uc] Control Circuit Voltage:
- 24 V AC 50/60 Hz
- Ambient Air Temperature For Storage:
- -60-80°C
- Warranty:
- 18 months
- [Ie] Rated Operational Current:
- 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Poles Description:
- 3P
- Irms Rated Making Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
- Pvc Free:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Toxic Heavy Metal Free:
- Yes
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Device Presentation:
- preassembled with reversing power busbar
- Overvoltage Category:
- III
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- [Icw] Rated Short-Time Withstand Current:
- 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Protective Cover:
- with
- Electrical Durability:
- 2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 12 A AC-3e <= 440 V
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Rohs Exemption Information:
- Yes
- Net Weight:
- 0.697 kg
- Circularity Profile:
- ENVEOLI1501004
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Product Or Component Type:
- reversing contactor
- Utilisation Category:
- AC-1 || AC-3 || AC-3e
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold