Schneider Electric LC2D40AG7 TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 40 A - coil 120 V AC 60 Hz
Schneider Electric
$667.08
LC2D40AG7 is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications. Rated 40A AC-3 18.5kW@400V, it includes a 120V 50/60Hz AC coil, 2NO+2NC aux contacts, a mechanical interlock. LC2D40AG7 is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications up to 18.5kW@400V. It includes a 120V 50/60Hz AC coil and 2NO+2NC built-in auxiliary contacts, NC mirror certified. Compact, DIN-rail mounting, with mechanical interlock and pre-wired reversing circuit, it procures reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 119mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with a 120V AC coil that can be supplied at 50Hz or 60Hz. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 1.6 million cycles at 40A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Power connections by EverLink BTR screw terminals providing constant tightening pressure.
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 60 A (at 60°C) for power circuit
- Contactor Application:
- motor control || resistive load
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Height:
- 122 mm
- Operating Time:
- 4...19 ms opening || 12...26 ms closing
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 60 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 60 Hz
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Maximum Horse Power Rating:
- 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 30 hp at 575/600 V AC 60 Hz for 3 phase motors || 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 3 hp at 115 V AC 60 Hz for 1 phase motors || 30 hp
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Control Circuit Type:
- AC 60 Hz
- Product Or Component Type:
- reversing contactor
- Inrush Power In Va:
- 140-140 VA 60 Hz cos phi 0.75 (at 20°C)
- Coil Technology:
- without built-in suppressor module
- Weight:
- 1.87 kg
- Depth:
- 120 mm
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Country of Origin:
- Mexico
- Pvc Free:
- Yes
- [Ie] Rated Operational Current:
- 40 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 60 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Rohs Exemption Information:
- Yes
- Mechanical Durability:
- 6 Mcycles
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Net Weight:
- 1.87 kg
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Device Short Name:
- LC2D
- Product Certifications:
- UL || CSA || RINA || GOST || CCC || DNV || LROS (Lloyds register of shipping) || GL || BV || UKCA
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Rated Breaking Capacity:
- 800 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Environmental Disclosure:
- ENVPEP1503009EN
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Fire Resistance:
- 850°C IEC 60695-2-1
- Protective Cover:
- with
- Toxic Heavy Metal Free:
- Yes
- [Uc] Control Circuit Voltage:
- 120 V AC 60 Hz
- Pollution Degree:
- 3
- Warranty:
- 18 months
- Range:
- TeSys || TeSys Deca
- Sustainable Offer Status:
- Green Premium product
- Utilisation Category:
- AC-3 || AC-1 || AC-3e