Schneider Electric

Schneider Electric LC2D80M7 TeSys Deca reversing contactor - 3P(3 NO) - AC-3/AC-3e - <= 440 V 80 A - 220 V AC coil

(No reviews yet) Write a Review
SKU:
LC2D80M7
MPN:
LC2D80M7
Condition:
New
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Device Presentation:
preassembled with reversing power busbar
Poles Description:
3P
Auxiliary Contact Composition:
1 NO + 1 NC
Control Circuit Type:
AC 50/60 Hz
Protective Treatment:
TH IEC 60068-2-30
Power Dissipation Per Pole:
12.5 W AC-1 || 5.1 W AC-3 || 5.1 W AC-3e
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1100 A at 440 V for power circuit conforming to IEC 60947
Depth:
158 mm
Inrush Power In Va:
245-245 VA 60 Hz cos phi 0.75 (at 20°C) || 245-245 VA 50 Hz cos phi 0.75 (at 20°C)
Fire Resistance:
850°C IEC 60695-2-1
Net Weight:
3.2 kg
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Range:
TeSys
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
[Icw] Rated Short-Time Withstand Current:
135 A 40°C - 10 min for power circuit || 320 A 40°C - 1 min for power circuit || 640 A 40°C - 10 s for power circuit || 990 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Environmental Disclosure:
ENVPEP110205EN
Sustainable Offer Status:
Green Premium product
Flame Retardance:
V1 conforming to UL 94
Pollution Degree:
3
Ambient Air Temperature For Storage:
-60-80°C
Device Short Name:
LC2D
Mercury Free:
Yes
Circularity Profile:
N/A
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || shocks contactor open8 Gn for 11 ms || vibrations contactor closed3 Gn, 5...300 Hz || shocks contactor closed10 Gn for 11 ms
Maximum Horse Power Rating:
20 hp at 200/208 V AC 60 Hz for 3 phase motors || 7.5 hp at 115 V AC 60 Hz for 1 phase motors || 15 hp at 230/240 V AC 60 Hz for 1 phase motors || 25 hp at 230/240 V AC 60 Hz for 3 phase motors || 60 hp at 460/480 V AC 60 Hz for 3 phase motors || 60
Insulation Resistance:
> 10 MOhm for Signaling circuit
Electrical Durability:
0.8 Mcycles 125 A AC-1 <= 440 V || 1.5 Mcycles 80 A AC-3 <= 440 V || 1.5 Mcycles 80 A AC-3e
Eu Rohs Directive:
Compliant
Sustainable Packaging:
Yes
Contactor Application:
motor control || resistive load
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Country of Origin:
Czechia
Maximum Operating Rate:
3600 cyc/h 60°C
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
Pole Contact Composition:
3 NO
Climatic Withstand:
IACS E10
[Ie] Rated Operational Current:
125 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 55 A (at <60°C) at <= 400 V AC AC-4 for power circuit
Pvc Free:
Yes
Mounting Support:
rail || plate
Toxic Heavy Metal Free:
Yes
Minimum Switching Voltage:
17 V for Signaling circuit
Product Name:
TeSys Deca
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Ip Degree Of Protection:
IP20 front face IEC 60529
Protective Cover:
with
$925.70

Description

LC2D80M7 is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications. Rated 80A AC-3 37kW@400V, it includes a 220V 50/60Hz AC coil, 2NO+2NC aux contacts, a mechanical interlock. LC2D80M7 is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications up to 37kW@400V. It includes a 220V 50/60Hz AC coil and 2NO+2NC built-in auxiliary contacts, NC mirror certified. Compact, DIN-rail mounting, with mechanical interlock and pre-wired reversing circuit, it procures reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 182mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with a 220V AC coil that can be supplied at 50Hz or 60Hz. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 1.2 million cycles at 80A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Connection by screw clamp terminals.
View AllClose