Schneider Electric

Schneider Electric LC2D95E7 TeSys Deca reversing contactor - 3P(3 NO) - AC-3/AC-3e - <= 440 V 95 A - 48 V AC coil

(No reviews yet) Write a Review
SKU:
LC2D95E7
MPN:
LC2D95E7
Condition:
New
Environmental Disclosure:
ENVPEP110205EN
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1100 A at 440 V for power circuit conforming to IEC 60947
Reach Free Of Svhc:
Yes
Operating Altitude:
0...9842.52 ft (0...3000 m)
Range:
TeSys
Country of Origin:
Czechia
Power Dissipation Per Pole:
12.5 W AC-1 || 7.2 W AC-3 || 7.2 W AC-3e
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Warranty:
18 months
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
[Ui] Rated Insulation Voltage:
power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || shocks contactor open8 Gn for 11 ms || vibrations contactor closed3 Gn, 5...300 Hz || shocks contactor closed10 Gn for 11 ms
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 125 A (at 60°C) for power circuit
Motor Power Kw:
25 kW at 220...230 V AC 50 Hz (AC-3) || 45 kW at 380...400 V AC 50 Hz (AC-3) || 45 kW at 415...440 V AC 50 Hz (AC-3) || 55 kW at 500 V AC 50 Hz (AC-3) || 45 kW at 660...690 V AC 50 Hz (AC-3) || 15 kW at 400 V AC 50 Hz (AC-4) || 25 kW at 220...230 V A
Protective Cover:
with
Safety Reliability Level:
B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1 || B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
Heat Dissipation:
6-10 W 50/60 Hz
Flame Retardance:
V1 conforming to UL 94
Hold-In Power Consumption In Va:
26-26 VA 60 Hz cos phi 0.3 (at 20°C) || 26-26 VA 50 Hz cos phi 0.3 (at 20°C)
Contactor Application:
resistive load || motor control
Insulation Resistance:
> 10 MOhm for Signaling circuit
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Circularity Profile:
N/A
[Uc] Control Circuit Voltage:
48 V AC 50/60 Hz
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
Mechanical Durability:
4 Mcycles
Coil Technology:
without built-in suppressor module
Climatic Withstand:
IACS E10
Product Certifications:
UL || CSA || RINA || GOST || CCC || DNV || LROS (Lloyds register of shipping) || GL || BV || UKCA
Pole Contact Composition:
3 NO
Inrush Power In Va:
245-245 VA 60 Hz cos phi 0.75 (at 20°C) || 245-245 VA 50 Hz cos phi 0.75 (at 20°C)
Product Or Component Type:
reversing contactor
[Icw] Rated Short-Time Withstand Current:
135 A 40°C - 10 min for power circuit || 400 A 40°C - 1 min for power circuit || 800 A 40°C - 10 s for power circuit || 1100 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Sustainable Offer Status:
Green Premium product
Control Circuit Type:
AC 50/60 Hz
Device Presentation:
preassembled with reversing power busbar
[Ie] Rated Operational Current:
125 A (at <60°C) at <= 690 V AC-1 for power circuit || 95 A (at <60°C) at <= 440 V AC-3 for power circuit || 95 A (at <60°C) at <= 440 V AC-3e for power circuit || 66.7 A (at <60°C) at <= 400 V AC-4 for power circuit
Ambient Air Temperature For Storage:
-60-80°C
Poles Description:
3P
Maximum Operating Rate:
3600 cyc/h 60°C
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Pvc Free:
Yes
Overvoltage Category:
III
Ip Degree Of Protection:
IP20 front face IEC 60529
Width:
182 mm
Net Weight:
3.2 kg
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Maximum Horse Power Rating:
20 hp at 200/208 V AC 60 Hz for 3 phase motors || 7.5 hp at 115 V AC 60 Hz for 1 phase motors || 15 hp at 230/240 V AC 60 Hz for 1 phase motors || 25 hp at 230/240 V AC 60 Hz for 3 phase motors || 60 hp at 460/480 V AC 60 Hz for 3 phase motors || 60
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-55°C operational AC 50 Hz || 0.85...1.1 Uc -40-55°C operational AC 60 Hz || 1...1.1 Uc 55-70°C operational AC 50/60 Hz
$1,114.40

Description

TeSys Deca reversing contactor, 3 poles (3NO), for motor control applications up to 95A/1000V AC-3/AC-3e (45kW@400V). It provides 48V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), connection by screw terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (182mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
View AllClose