Schneider Electric

Schneider Electric LRD08 TeSys Deca, thermal overload relay, 2.5 to 4 A, class 10A

(No reviews yet) Write a Review
SKU:
LRD08
MPN:
LRD08
Condition:
New
Warranty:
18 months
Eu Rohs Directive:
Compliant
Connections - Terminals:
control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end || power circuit
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Mechanical Robustness:
vibrations6 Gn IEC 60068-2-6 || shocks15 Gn for 11 ms IEC 60068-2-7
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Weight:
0.124 kg
Toxic Heavy Metal Free:
Yes
[Ue] Rated Operational Voltage:
690 V AC 0...400 Hz power circuit IEC 60947-4-1
Product Name:
TeSys LRD || TeSys Deca
Auxiliary Contact Composition:
1 NO + 1 NC
Permissible Current:
3 A 120 V AC-15 Signaling circuit || 0.22 A 125 V DC-13 Signaling circuit
Net Weight:
0.124 kg
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5 || EN 50495
Control Type:
Red push-button stop || Blue push-button reset
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals || power circuit 1.7 N.m screw clamp terminals
Circularity Profile:
ENVEOLI0802006
Depth:
70 mm
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Dielectric Strength:
1.89 kV 50 Hz IEC 60947-1
Environmental Disclosure:
ENVPEP080206EN
Associated Fuse Rating:
4 A gG for Signaling circuit || 4 A BS for Signaling circuit
Ip Degree Of Protection:
IP20 conforming to IEC 60529
Thermal Protection Adjustment Range:
2.5-4 A
Sustainable Offer Status:
Green Premium product
Tripping Threshold:
1.14 +/- 0.06 Ir IEC 60947-4-1
Device Short Name:
LRD
Ambient Air Temperature For Operation:
-20-60°C without derating IEC 60947-4-1
Mounting Support:
plate, with specific accessories || rail, with specific accessories || under contactor
Network Type:
AC || DC
Relay Application:
motor protection
Mercury Free:
Yes
[Uimp] Rated Impulse Withstand Voltage:
6 kV
Climatic Withstand:
IACS E10
Flame Retardance:
V1 conforming to UL 94
Temperature Compensation:
-20-60°C
Country of Origin:
France
Product Or Component Type:
differential thermal overload relay
Ambient Air Temperature For Storage:
-60-70°C
Range:
TeSys || TeSys Deca
Network Frequency:
0...400 Hz
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Product Compatibility:
LC1D12 || LC1D09 || LC1D25 || LC1D38 || LC1D32 || LC1D18
[Ith] Conventional Free Air Thermal Current:
5 A Signaling circuit
Phase Failure Sensitivity:
tripping current 130 % of Ir on two phase, the last one at 0
$60.00

Description

TeSys LRD overload relays are designed to be used with TeSys D contactors to make a motor starter. This overload relay can be used with 9 amp through 38 amp TeSys D contactors. These differential thermal overload relays detect over currents in the lines to the motor. When an overcurrent is detected the overload relay working with the contactor will disconnect the power to the motor. This will minimize the damage to the motor windings. This overload relay has an adjustable trip current rating of 2.5 to 4.0 amperes. This trip current rating is calibrated per Class 10A. Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).