Schneider Electric

Schneider Electric LTMR100EFM Motor controller, TeSys T, Motor Management, Ethernet/IP, Modbus/TCP, 6 inputs, 3 outputs, 5 to 100A, 100 to 240VAC

(No reviews yet) Write a Review
SKU:
LTMR100EFM
MPN:
LTMR100EFM
Condition:
New
Mercury Free:
Yes
Warranty:
18 months
Measurement Accuracy:
5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 5 % active and reactive power || 0,02 current
Ip Degree Of Protection:
IP20
Connections - Terminals:
control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cab
Ambient Air Temperature For Storage:
-40-80°C
Range:
TeSys
Width:
91 mm
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Pollution Degree:
3
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Pvc Free:
Yes
Depth:
122.5 mm
Mechanical Robustness:
vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
Load Current:
5 A 250 V AC logic output || 5 A 30 V DC logic output
[Us] Rated Supply Voltage:
100...240 V AC 50/60 Hz
Web Services:
web server
Associated Fuse Rating:
4 A gG output || 0.5 A gG control circuit
Contacts Type And Composition:
1 NO + 1 NC fault signal || 3 NO
Fire Resistance:
650°C EN/IEC 60695-2-12 || 960°C UL 94
Bus Type:
Ethernet IEEE 802.3 0...159 10...100 Mbit/s, RJ45 2 shielded twisted pairs
Device Short Name:
LTMR
Network And Machine Diagnosis Type:
waiting time after overload tripping || motor control command recording || trip context information || phase fault and earth fault trip counters || starting current and time || trip history information || fault recording || event recording || remaini
Logic Input Number:
6
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || IACS E10 || UL 508 || IEC 60947-4-1
Overvoltage Category:
III
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Connection Pitch:
5.08 mm
Short-Circuit Withstand:
100 kA conforming to EN/IEC 60947-4-1
Weight:
0.53 kg
Current Consumption:
8...62.8 mA
Circularity Profile:
ENVEOLI100411EN_V2
Eu Rohs Directive:
Compliant with Exemptions
[Uimp] Rated Impulse Withstand Voltage:
4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1
Maximum Operating Rate:
1800 cyc/h
Height:
61 mm
Input Current:
3.1 mA 100 V || 7.5 mA 240 V
Halogen Content Performance:
Halogen free plastic parts product
Product Certifications:
C-tick || ABS || UL || DNV || NOM || RINA || RMRoS || BV || LROS (Lloyds register of shipping) || KERI || EAC || CCC || CSA || ATEX || GL
Permissible Power:
480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Supply Voltage Limits:
93.5-264 V AC
Operating Altitude:
<= 6561.68 ft (2000 m) without derating
Product Name:
TeSys T
Sustainable Offer Status:
Green Premium product
Measurement Current:
5-100 A
Current State 0 Guaranteed:
logic input 0...40 V <= 15 mA 25 ms
Metering Type:
phase current I1, I2, I3 RMS || temperature || earth-fault current || average current Iavg || imbalance current
Protective Treatment:
12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
Environmental Disclosure:
ENVPEP060308EN_V2
Maximum Operating Frequency:
2 Hz
$1,025.00

Description

TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. Ethernet/IP and Modbus/TCP protocol is used by this controller. Ethernet TCP/IP communication is used. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 5 to 100 amperes. 120 to 240 VAC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
View AllClose