This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 16A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- [Ui] Rated Insulation Voltage:
- 500 V AC 50/60 Hz EN/IEC 60947-2
- Mechanical Durability:
- 20000 cycles
- Device Short Name:
- C60N
- Net Weight:
- 0.24 kg
- Eu Rohs Directive:
- Compliant with Exemptions
- Curve Code:
- D
- Local Signalling:
- ON/OFF indication
- Line Rated Current:
- 16 A 50 °C EN/IEC 60947-2
- Tightening Torque:
- 2-2 N.m top or bottom
- Network Type:
- DC || AC
- Color:
- Gray
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kVEN/IEC 60947-2
- Mounting Support:
- DIN rail
- Provision For Padlocking:
- padlockable
- Electrical Durability:
- 10000 cycles
- Ambient Air Temperature For Operation:
- -30-70 °C
- Range:
- Multi9
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Mercury Free:
- Yes
- Trip Unit Technology:
- thermal-magnetic
- Sustainable Offer Status:
- Green Premium product
- Limitation Class:
- 3
- Device Application:
- distribution
- Product Certifications:
- EAC || KC || CCC
- Product Or Component Type:
- miniature circuit-breaker
- Depth:
- 72 mm
- Relative Humidity:
- 95-95 % 55-55 °C
- Height:
- 81 mm
- Utilisation Category:
- category A EN/IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Control Type:
- toggle
- 9 Mm Pitches:
- 4
- Halogen Content Performance:
- Halogen free product
- Environmental Disclosure:
- ENVPEP1304004EN
- Connections - Terminals:
- tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
- Overvoltage Category:
- IV
- [Ics] Rated Service Breaking Capacity:
- 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 20 kA 100 % EN/IEC 60947-2 - <= 125 V DC
- Earth-Leakage Protection:
- separate block
- Standards:
- EN/IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Contact Position Indicator:
- yes
- Ambient Air Temperature For Storage:
- -40-80 °C
- Pollution Degree:
- 3 EN/IEC 60947-2
- Circularity Profile:
- N/A
- Number Of Protected Poles:
- 2
- Breaking Capacity:
- 20 kA Icu <= 125 V DC EN/IEC 60947-2 || 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
- Mounting Mode:
- clip-on
- [Ue] Rated Operational Voltage:
- 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 125 V DC
- Heat Dissipation:
- 5-5 W 415 V - 16 A
- Product Name:
- Multi9 C60
- Rohs Exemption Information:
- Yes
- Wire Stripping Length:
- 14 mm for top or bottom connection
- Magnetic Tripping Limit:
- 12 x In +/- 20 % AC || 17 x In +/- 20 % DC
- Tropicalisation:
- 2 IEC 60068-1
- Poles Description:
- 2P
- Width:
- 36 mm
- Brochure:
- View
- Datasheet:
- View