Schneider Electric M9F12304 Multi9 C60N 3P D 4A 10Ka 415V Mcb
Schneider Electric
$300.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 4A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 81mm x (D) 72mm. The weight is 0.36kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
- Halogen Content Performance:
- Halogen free product
- Overvoltage Category:
- IV
- Tropicalisation:
- 2 IEC 60068-1
- Mechanical Durability:
- 20000 cycles
- Depth:
- 72 mm
- Circularity Profile:
- N/A
- Heat Dissipation:
- 7.2-7.2 W 415 V - 4 A
- [Ue] Rated Operational Voltage:
- 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 125 V DC
- Provision For Padlocking:
- padlockable
- Height:
- 81 mm
- [Ics] Rated Service Breaking Capacity:
- 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 30 kA 100 % EN/IEC 60947-2 - <= 125 V DC
- [Ui] Rated Insulation Voltage:
- 500 V AC 50/60 Hz EN/IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kVEN/IEC 60947-2
- Tightening Torque:
- 2-2 N.m top or bottom
- Poles Description:
- 3P
- Trip Unit Technology:
- thermal-magnetic
- Network Frequency:
- 50/60 Hz
- Local Signalling:
- ON/OFF indication
- Ambient Air Temperature For Storage:
- -40-80 °C
- Sustainable Offer Status:
- Green Premium product
- Pollution Degree:
- 3 EN/IEC 60947-2
- Ambient Air Temperature For Operation:
- -30-70 °C
- Control Type:
- toggle
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Limitation Class:
- 3
- Curve Code:
- D
- Environmental Disclosure:
- ENVPEP1304004EN
- Contact Position Indicator:
- yes
- Net Weight:
- 0.36 kg
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Number Of Protected Poles:
- 3
- Range:
- Multi9
- Earth-Leakage Protection:
- separate block
- Width:
- 54 mm
- Utilisation Category:
- category A EN/IEC 60947-2
- Device Short Name:
- C60N
- 9 Mm Pitches:
- 6
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Line Rated Current:
- 4 A 50 °C EN/IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Connections - Terminals:
- tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
- Mounting Mode:
- clip-on
- Relative Humidity:
- 95-95 % 55-55 °C
- Wire Stripping Length:
- 14 mm for top or bottom connection
- Product Certifications:
- EAC || KC || CCC
- Standards:
- EN/IEC 60947-2
- Product Or Component Type:
- miniature circuit-breaker
- Mounting Support:
- DIN rail
- Product Name:
- Multi9 C60
- Network Type:
- DC || AC
- Device Application:
- distribution
- Electrical Durability:
- 10000 cycles
- Magnetic Tripping Limit:
- 12 x In +/- 20 % AC || 17 x In +/- 20 % DC
- Mercury Free:
- Yes
- Rohs Exemption Information:
- Yes
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Color:
- Gray
- Breaking Capacity:
- 30 kA Icu <= 125 V DC EN/IEC 60947-2 || 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
- Brochure:
- View
- Datasheet:
- View