Schneider Electric

Schneider Electric PGL26120 Molded Case Circuit Breaker 600V 1200A

(No reviews yet) Write a Review
SKU:
PGL26120
UPC:
785901787143
Condition:
New
[Ics] Rated Service Breaking Capacity:
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Ambient Air Temperature For Storage:
-50-85 °C
Mercury Free:
Yes
Poles Description:
2P
Pollution Degree:
3 IEC 60947-1
Trip Unit Name:
ET 1.0I
Product Name:
PowerPact P
Ip Degree Of Protection:
front cover IP40
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Eu Rohs Directive:
Compliant with Exemptions
Environmental Disclosure:
ENVPEP2206033EN
Ambient Air Temperature For Operation:
-2-70 °C
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Height:
16.16 in
Range:
PowerPact
Awg Gauge:
4 x AWG 3/0...500 kcmil aluminium/copper
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Continuous Current Rating:
0.8
Quantity Per Set:
1
Line Rated Current:
1200-1200 A
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Trip Unit Technology:
electronic, basic, ET 1.0I, I
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Breaking Capacity Code:
G
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Product Or Component Type:
circuit breaker
Circularity Profile:
ENVEOLI2206033EN
Net Weight:
32 lb(US)
Depth:
8.05 in
Electrical Connection:
lugs, line || lugs, load
Wire Stripping Length:
30 mm
Local Signalling:
1 trip indicator green)
Terminal Identifier:
AL1200P25K
Rohs Exemption Information:
Yes
Product Certifications:
UL || CSA || NOM
Network Frequency:
50/60 Hz
Breaking Capacity:
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
Control Type:
toggle
Mounting Support:
lug
Circuit Breaker Application:
HACR rated
Mounting Mode:
unit mount lug)
Pvc Free:
Yes
Sustainable Offer Status:
Green Premium product
Long Time Pick-Up Adjustment Range:
1 In
Device Application:
distribution
Tightening Torque:
50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Quality Labels:
CE
Warranty:
18 months
Width:
8.27 in
Brochure:
View
Catalog:
View
Datasheet:
View
$17,363.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has an electronic trip unit, ET 1.0I. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 1200A, 2 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose