Schneider Electric

Schneider Electric PJA36040CU33A Circuit breaker, PowerPacT P, 400A, 3 pole, 600VAC, 25kA, I-Line, Micrologic 5.0, 100%, ABC

(No reviews yet) Write a Review
SKU:
PJA36040CU33A
MPN:
PJA36040CU33A
Condition:
New
Product Name:
PowerPact P
Length:
25 mm
Control Type:
toggle
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Poles Description:
3P
Rohs Exemption Information:
Yes
Breaking Capacity Code:
J
Trip Unit Technology:
electronic, standard, MicroLogic 5.0, LSI
Network Frequency:
50/60 Hz
Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
Circuit Breaker Application:
HACR rated
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Wire Stripping Length:
25 mm
Terminal Identifier:
AL800M23K
Pvc Free:
Yes
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Depth:
8.05 in
Sustainable Offer Status:
Green Premium product
Product Certifications:
UL || CSA || NOM
Quantity Per Set:
1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Height:
9 in
Environmental Disclosure:
ENVPEP2206033EN
Height:
12.86 in
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Weight:
32 lb(US)
Mounting Support:
bracket
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Mounting Height:
9 in
Electrical Connection:
I-Line connection, line || lugs, load
Device Application:
distribution
Range:
PowerPact
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Phase Connection:
ABC
Circularity Profile:
ENVEOLI2206033EN
Country of Origin:
United States
Quality Labels:
CE
Mounting Mode:
I-Line bracket)
Ambient Air Temperature For Storage:
-50-85°C
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Eu Rohs Directive:
Compliant with Exemptions
Pollution Degree:
3 IEC 60947-1
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Continuous Current Rating:
1
Net Weight:
32 lb(US)
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Local Signaling:
1 trip indicator green)
$24,231.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard with a 5.0 trip unit and an LSI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT P, 400A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 100% with an ABC phase connection. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose