Schneider Electric

Schneider Electric PKL36080CU43A Circuit breaker, PowerPacT P, 800A, 3 pole, 600VAC, 65kA, lugs, Micrologic 5.0A, 100%

(No reviews yet) Write a Review
SKU:
PKL36080CU43A
MPN:
PKL36080CU43A
Condition:
New
Local Signaling:
overload 1 trip indicator green) || 1 trip indicator green) || trip causes 1 trip indicator green)
Trip Unit Technology:
electronic, ammeter, MicroLogic 5.0 A, LSI
Length:
25 mm
Circuit Breaker Application:
HACR rated
Sustainable Offer Status:
Green Premium product
Environmental Disclosure:
ENVPEP1407012EN
Suitability For Isolation:
yes IEC 60947-2
Product Or Component Type:
circuit breaker
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Wire Stripping Length:
25 mm
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Breaking Capacity Code:
K
Rohs Exemption Information:
Yes
Mercury Free:
Yes
Device Application:
distribution
Net Weight:
32 lb(US)
Electrical Connection:
lugs, line || lugs, load
Terminal Identifier:
AL800M23K
Utilisation Category:
category A
Ip Degree Of Protection:
front cover IP40
Pollution Degree:
3 IEC 60947-1
Pvc Free:
Yes
Quality Labels:
CE
Weight:
32 lb(US)
Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
Country of Origin:
Mexico
Product Certifications:
UL || CSA || NOM
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Warranty:
18 months
Depth:
8.05 in
[Ics] Rated Service Breaking Capacity:
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
Network Frequency:
50/60 Hz
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Mounting Mode:
unit mount lug)
Range:
PowerPact
Ambient Air Temperature For Storage:
-50-85°C
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Control Type:
toggle
Quantity Per Set:
1
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mounting Support:
lug
Breaking Capacity:
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 50 kA 480 V AC 50/60 Hz UL 489 || AIR 50 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Product Name:
PowerPact P
Line Rated Current:
800-800 A
Trip Unit Name:
MicroLogic 5.0 A
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
$25,085.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Ammeter with a 5.0A trip unit and an LSI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 800A, 3 pole, circuit breaker has an interrupting rating of 50kA at 600VAC. This circuit breaker has a continuous current rating of 100%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose