Schneider Electric

Schneider Electric VLS3P100R2 Disconnect switch, TeSys VLS, body switch, 100A, 50HP at 480VAC, UL98, three phase, 50kA SCCR, size 2, DIN rail mount

(No reviews yet) Write a Review
SKU:
VLS3P100R2
MPN:
VLS3P100R2
Condition:
New
Control Type:
rotary handle
[Ith] Conventional Free Air Thermal Current:
100 A (at 55°C)
Intermittent Duty Class:
class 120 - 60 %
[Uimp] Rated Impulse Withstand Voltage:
8 kV
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 508
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Contacts Type And Composition:
3 NO
Handle Colour:
black
Country of Origin:
United States
Product Name:
TeSys VARIO LS
[Ie] Rated Operational Current:
100 A Ue: 600 V UL98 || 100 A AC-21A Ue: 400 V || 100 A AC-21A Ue: 500 V || 100 A AC-21A Ue: 690 V || 100 A AC-22A Ue: 400 V || 100 A AC-22A Ue: 500 V || 100 A AC-22A Ue: 690 V || 100 A AC-23A Ue: 400 V || 80 A AC-23A Ue: 500 V || 47 A AC-23A Ue: 690
Electrical Durability:
30000 cycles AC-21
Suitability For Isolation:
yes
Mechanical Durability:
30000 cycles
Breaking Capacity:
150 A 690 V AC-21A) || 300 A 690 V AC-22A) || 800 A 690 V AC-23A)
Marking:
0 - 1
Device Composition:
handle || switch
Performance Level:
high performance
Weight:
0.365 kg
Product Certifications:
cULus || GL
[Icm] Rated Short-Circuit Making Capacity:
3550 A 690 V
Handle Front Plate Colour:
grey
Rated Operational Power In W:
55 kW 400 V AC-23A) || 45 kW 500 V AC-23A) || 45 kW 690 V AC-23A)
Color:
Gray
Rohs Exemption Information:
Yes
Net Weight:
0.365 kg
Mercury Free:
Yes
[Ithe] Conventional Enclosed Thermal Current:
100 A
Reach Free Of Svhc:
Yes
Range:
TeSys
Device Short Name:
VLS3P
Toxic Heavy Metal Free:
Yes
Network Type:
AC
[Icw] Rated Short-Time Withstand Current:
2500 A 690 V 1 s
Fire Resistance:
960°C IEC 60695-2-11
Rated Conditional Short-Circuit Current:
50 kA 400 V 100 A gG
Rotary Handle Mounting Style:
direct
Fixing Mode:
by clips back
Making Capacity:
150 A 690 V AC-21A || 300 A 690 V AC-22A || 1000 A 690 V AC-23A
Network Frequency:
50/60 Hz
Standards:
UL98 || CSA C22.2 No 4 || IEC 60947-3
Ambient Air Temperature For Operation:
-25-55°C
Ip Degree Of Protection:
IP20 conforming to IEC 60529
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Tightening Torque:
power circuit 5-6 N.m screw clamp terminals
Compatibility Code:
VLS
$145.63

Description

These TeSys VLS disconnect switches are for integration into control systems in applications like material handling, HVAC, pumping, solar energy, mining and many more. This family of disconnect switches has switches ranging from 16A to 125A. The 16A, 25A, 32A, 40A and 63A disconnect switches are UL508 motor disconnect switches rated. The 63A, 80A, 100A and 125A disconnect switches are UL98 non fusible disconnect switch rated. This 100A disconnect switch has 3 normally open poles and mounts on DIN rail. Per UL and CSA this this disconnect switch has a 5 HP rating at 120 VAC and a 10 HP at 240 VAC single phase. Per UL and CSA this disconnect switch has a 30 HP rating at 200 to 208 VAC and 240 VAC, a 50 HP rating at 480 VAC and 600 VAC three phase. Per UL508A this this disconnect switch has up to a 50 kA at 600 V short circuit current rating (SCCR) with a 100A Type J fuse maximum. Per IEC requirements, this disconnect switch has a 55 kW rating at 400 V, a 45 kW rating at 500 V and a 45 kW rating at 690V three phase. The screw clamp terminals will accept 10 mm solid or 16 mm stranded wire. The clamps will also accept from 12 AWG to 1 AWG wire. This disconnect switch is 3.94 inches tall, 2.75 inches wide and 2.95 inches deep. The switch weighs 0.80 lbs. There are many handles and accessories available this TeSys VLS disconnect switch. This TeSys VLS disconnect switch is UL Listed per UL98, CSA certified per CSA 22.2 and meets IEC 60947-3 requirements.