WAGO 750-663/000-003 4-Channel Intrinsically Safe Digital Input Module
Wago
Technical Data
- Number of digital inputs: 4
- Total number of channels (module): 4
- Achievable safety classes: SIL 3 acc. to IEC 61508; SIL 3 acc. to IEC 61511; SIL 3 acc. to IEC 62061; Cat. 4, PL e acc. to EN ISO 13849
- Type of signal: Voltage
- Type of signal voltage: DC 24 V
- Sensor connection: 4 x (sicherer Eingang mit Testpuls)
- Input characteristic: Type 1
- Input filter (digital): 0 ms
- Input filter: 0 ms 200 ms, configurable in steps
- Input filter: parametrizable (channel by channel): yes
- Input current per channel for signal (1) typ.: 3 mA
- Output current per channel: 0.05 A
- Short-circuit current: 25 mA
- Signal frequency max.: 50 Hz
- Intrinsic safety Ex i: yes
- System supply voltage: DC 5 V; via data contacts
- Current consumption, system supply (5 V): 145 mA
- Field supply voltage: DC 24 V; (Versorgung ber Einspeisung Ex i U<sub>O</sub> = max. 27,3 V); ber Leistungskontakte (Einspeisung ber Messerkontakt; Weiterleitung ber Federkontakt)
- Current consumption, field supply (module with no external load): 20 mA
- Isolation: 300 VAC system/field
- Indicators: LED (A-D) green/red: Status/Error I1 I4; LED (E) red: Group error; LED (F-H) green/red: Diagnostics
- Number of incoming power jumper contacts: 2
- Number of outgoing power jumper contacts: 2
- Current carrying capacity of the power jumper contacts: 1 A
- Ex guideline: EN/IEC 60079-0, -7, -11, -26, -31
- Electric circuit, safety-relevant data: U<sub>o</sub> = 27.3 V; I<sub>o</sub> = 23 mA; P<sub>o</sub> = 157 mW; Characteristic: Linear
- Reactances Ex ia IIC: L<sub>o</sub> = 61 mH; C<sub>o</sub> = 64 nF
- Reactances Ex ia IIB: L<sub>o</sub> = 100 mH; C<sub>o</sub> = 552 nF
- Ex ia IIA reactances: L<sub>o</sub> = 100 mH; C<sub>o</sub> = 2,28 F
- Reactances Ex ia I: L<sub>o</sub> = 100 mH; C<sub>o</sub> = 2.95 F
- Reactances: (The above-listed ratings do not account for the coincidental occurrence of capacitances and inductances. For ratings taking the coincidental occurrence of capacitances and inductances into account, see manual)
- Marking: ATEX, IECEx, Underwriters Laboratories Inc.
Connection Data
- Connection technology: In-/Outputs: 8 x CAGE CLAMP<sup></sup>
- Connection type (1): Inputs/Outputs
- Solid conductor: 0.08 2.5 mm / 28 14 AWG
- Fine-stranded conductor: 0.08 2.5 mm / 28 14 AWG
- Strip length: 8 9 mm / 0.31 0.35 inch
- Anschlussanforderung zul¤ssige Leitungsl¤nge: 100 m
Geometrical Data
- Width: 24 mm / 0.945 inch
- Height: 67.8 mm / 2.669 inch
- Height from upper-edge of DIN-35 rail: 60.6 mm / 2.386 inch
- Depth: 100 mm / 3.937 inch
Mechanical Data
- Type of mounting: DIN-35 rail
Material Data
- Color: multicoloured
- Housing material: Polycarbonate, polyamide 6.6
- Fire load: 0.000 MJ
- Weight: 91.988 g
- Conformity marking: CE
Environmental Requirements
- Surrounding air (operating) temperature: 0 55 C
- Surrounding air (storage) temperature: -40 85 C
- Protection class: IP20
- Degree of pollution (5): 2 per IEC 61131-2
- Operating altitude: 0 2000 m
- Mounting position: horizontal (standing/lying) or vertical
- Relative air humidity (no condensation): 95 %
- Vibration resistance: 4g per IEC 60068-2-6
- Shock resistance: 15g per IEC 60068-2-27
- EMC immunity to interference: acc. to EN 61000-6-2, marine applications
- EMC emission of interference: acc. to EN 61000-6-3, marine applications
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Permissible H<sub>2</sub>S contaminant concentration at a relative humidity <lt/> 75 %: 10 ppm
- Permissible SO<sub>2</sub> contaminant concentration at a relative humidity <lt/> 75 %: 25 ppm
Commercial data
- Packaging type: BOX
- Country of origin: DE
- GTIN: 4050821531432
- Customs Tariff No.: 85389099990
The WAGO 750 series intrinsically-safe DC digital input slice module is designed for high safety applications (SIL3/Cat4/PLe) and features 4 fail-safe digital inputs with test pulse capabilities, adjustable input filters, and PROFIsafe V2 iPar communication. It operates on a 5Vdc supply provided by the system, uses spring CAGE CLAMP connections, and mounts on a DIN-35 rail with a 24mm width. The module is rated for ambient temperatures from 0°C to +55°C, has an IP20 protection rating, and complies with standards IEC61508, IEC62061, EN ISO13849, and EN 61511. It is equivalent to model 750663000003.
- color:
- Multicoloured
- configuration options:
- PROFIsafe address adjustable via DIP switch or engineering software
- conformity marking:
- CE
- connection requirement permissible cable length:
- 100 m
- connection technology inputs outputs:
- 8 x CAGE CLAMP
- connection type 1:
- Inputs/outputs
- country of origin sales organisation germany:
- DE
- current carrying capacity power jumper contacts:
- 0.0416666666666667
- depth:
- 67.8 mm / 2.669 inch
- depth from upper edge of din rail:
- 60.6 mm / 2.386 inch
- emc emission of interference:
- Per EN 61000-6-3, marine applications
- emc immunity to interference:
- Per EN 61000-6-2, marine applications
- ex guideline:
- EN IEC 60079-0, -7, -11
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.08 2.5 mm / 28 14 AWG
- fire load:
- 1.685 MJ
- height:
- 100 mm / 3.937 inch
- housing material:
- Polycarbonate: polyamide 6.6
- indicators:
- LED (A-D) green/red: Status/Error I1 I4: LED (E) red: Group error: LED (F-H) green/red: Diagnostics
- input characteristic:
- Clock sensitive || Type 1
- input current per channel for signal 1 typ:
- 3 mA
- input filter:
- 0 200 ms (parameterizable in steps)
- input filter digital:
- 0.5 ms || 1 ms || 2 ms || 3 ms || 5 ms || 10 ms || 20 ms || 50 ms || 100 ms || 200 ms || 0 ms
- input filter parametrizable channel by channel:
- Yes
- intrinsic safety ex i:
- Yes
- isolation:
- 300 VAC system/field
- marking:
- ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc: II (1) D [Ex ia Da] IIIC: I (M1) [Ex ia Ma] I
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- number of digital inputs:
- 4
- number of incoming power jumper contacts:
- 2
- number of outgoing power jumper contacts:
- 2
- operating altitude:
- 0 2000 m
- output current per channel:
- 0.05 A
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per IEC 61131-2
- power consumption 5 v system supply:
- 145 mA
- power consumption field supply module with no external load:
- 20 mA
- protection type:
- IP20
- reactances ex ia i:
- Lo = 100 mH: Co = 2.95 F
- reactances ex ia iia:
- Lo = 100 mH: Co = 2,28 F
- reactances ex ia iib:
- Lo = 100 mH: Co = 552 nF
- reactances ex ia iic:
- Lo = 61 mH: Co = 64 nF
- reactances note:
- (The above-listed ratings do not account for the coincidental occurrence of capacitances and inductances. For ratings taking the coincidental occurrence of capacitances and inductances into account, see manual)
- relative humidity without condensation:
- 0.95
- safety relevant data circuit:
- Uo = 27.3 V: Io = 23 mA: Po = 157 mW: Characteristic: Linear
- sensor connection:
- 4 x (Fail-safe input with test pulse)
- shock resistance:
- 15g per IEC 60068-2-27
- short circuit current:
- ¤ 25 mA
- signal frequency max:
- 50 Hz
- signal type:
- Voltage
- solid conductor:
- 0.08 2.5 mm / 28 14 AWG
- strip length:
- 8 9 mm / 0.31 0.35 inch
- supply voltage field:
- 24 VDC: (Ex i power supply: UO = max. 27.3 V): via power jumper contacts (power supply via blade contact: transmission via spring contact)
- supply voltage system:
- 5 VDC: via data contacts
- surrounding air temperature operation:
- 0 55 C
- surrounding air temperature storage:
- -40 85 C
- total number of channels module:
- 4
- vibration resistance:
- 4g per IEC 60068-2-6
- voltage signal type:
- 24 VDC
- weight:
- 91.988 g
- width:
- 24 mm / 0.945 inch