WAGO 750-663/000-003

(No reviews yet) Write a Review
SKU:
750-663/000-003
MPN:
750-663/000-003
Condition:
New
color:
Multicoloured
configuration options:
PROFIsafe address adjustable via DIP switch or engineering software
conformity marking:
CE
connection requirement permissible cable length:
100 m
connection technology inputs outputs:
8 x CAGE CLAMP
connection type 1:
Inputs/outputs
country of origin sales organisation germany:
DE
current carrying capacity power jumper contacts:
0.0416666666666667
depth:
67.8 mm / 2.669 inch
depth from upper edge of din rail:
60.6 mm / 2.386 inch
emc emission of interference:
Per EN 61000-6-3, marine applications
emc immunity to interference:
Per EN 61000-6-2, marine applications
ex guideline:
EN IEC 60079-0, -7, -11
exposure to pollutants:
Per IEC 60068-2-42 and IEC 60068-2-43
fine stranded conductor:
0.08 2.5 mm / 28 14 AWG
fire load:
1.685 MJ
height:
100 mm / 3.937 inch
housing material:
Polycarbonate: polyamide 6.6
indicators:
LED (A-D) green/red: Status/Error I1 I4: LED (E) red: Group error: LED (F-H) green/red: Diagnostics
input characteristic:
Clock sensitive || Type 1
input current per channel for signal 1 typ:
3 mA
input filter:
0 200 ms (parameterizable in steps)
input filter digital:
0.5 ms || 1 ms || 2 ms || 3 ms || 5 ms || 10 ms || 20 ms || 50 ms || 100 ms || 200 ms || 0 ms
input filter parametrizable channel by channel:
Yes
intrinsic safety ex i:
Yes
isolation:
300 VAC system/field
marking:
ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc: II (1) D [Ex ia Da] IIIC: I (M1) [Ex ia Ma] I
mounting position:
Horizontal (standing/lying): vertical
mounting type:
DIN-35 rail
number of digital inputs:
4
number of incoming power jumper contacts:
2
number of outgoing power jumper contacts:
2
operating altitude:
0 2000 m
output current per channel:
0.05 A
packaging type:
Box
permissible h2s contaminant concentration at a relative humidity 75:
10 ppm
permissible so2 contaminant concentration at a relative humidity 75:
25 ppm
pollution degree 5:
2 per IEC 61131-2
power consumption 5 v system supply:
145 mA
power consumption field supply module with no external load:
20 mA
protection type:
IP20
reactances ex ia i:
Lo = 100 mH: Co = 2.95 F
reactances ex ia iia:
Lo = 100 mH: Co = 2,28 F
reactances ex ia iib:
Lo = 100 mH: Co = 552 nF
reactances ex ia iic:
Lo = 61 mH: Co = 64 nF
reactances note:
(The above-listed ratings do not account for the coincidental occurrence of capacitances and inductances. For ratings taking the coincidental occurrence of capacitances and inductances into account, see manual)
relative humidity without condensation:
0.95
safety relevant data circuit:
Uo = 27.3 V: Io = 23 mA: Po = 157 mW: Characteristic: Linear
sensor connection:
4 x (Fail-safe input with test pulse)
shock resistance:
15g per IEC 60068-2-27
short circuit current:
¤ 25 mA
signal frequency max:
50 Hz
signal type:
Voltage
solid conductor:
0.08 2.5 mm / 28 14 AWG
strip length:
8 9 mm / 0.31 0.35 inch
supply voltage field:
24 VDC: (Ex i power supply: UO = max. 27.3 V): via power jumper contacts (power supply via blade contact: transmission via spring contact)
supply voltage system:
5 VDC: via data contacts
surrounding air temperature operation:
0 55 C
surrounding air temperature storage:
-40 85 C
total number of channels module:
4
vibration resistance:
4g per IEC 60068-2-6
voltage signal type:
24 VDC
weight:
91.988 g
width:
24 mm / 0.945 inch
  • Wago 750-663/000-003
  • Wago 750-663/000-003
  • Wago 750-663/000-003
$1,365.00

Description

Intrinsically safe 4-channel digital input; 24 VDC; PROFIsafe V2.0 iPar

Technical Data
  • Number of digital inputs: 4
  • Total number of channels (module): 4
  • Achievable safety classes: SIL 3 acc. to IEC 61508; SIL 3 acc. to IEC 61511; SIL 3 acc. to IEC 62061; Cat. 4, PL e acc. to EN ISO 13849
  • Type of signal: Voltage
  • Type of signal voltage: DC 24 V
  • Sensor connection: 4 x (sicherer Eingang mit Testpuls)
  • Input characteristic: Type 1
  • Input filter (digital): 0 ms
  • Input filter: 0 ms ˜ 200 ms, configurable in steps
  • Input filter: parametrizable (channel by channel): yes
  • Input current per channel for signal (1) typ.: 3 mA
  • Output current per channel: 0.05 A
  • Short-circuit current: 25 mA
  • Signal frequency max.: 50 Hz
  • Intrinsic safety Ex i: yes
  • System supply voltage: DC 5 V; via data contacts
  • Current consumption, system supply (5 V): 145 mA
  • Field supply voltage: DC 24 V; (Versorgung ber Einspeisung Ex i U<sub>O</sub> = max. 27,3 V); ber Leistungskontakte (Einspeisung ber Messerkontakt; Weiterleitung ber Federkontakt)
  • Current consumption, field supply (module with no external load): 20 mA
  • Isolation: 300 VAC system/field
  • Indicators: LED (A-D) green/red: Status/Error I1 ˜ I4; LED (E) red: Group error; LED (F-H) green/red: Diagnostics
  • Number of incoming power jumper contacts: 2
  • Number of outgoing power jumper contacts: 2
  • Current carrying capacity of the power jumper contacts: 1 A
  • Ex guideline: EN/IEC 60079-0, -7, -11, -26, -31
  • Electric circuit, safety-relevant data: U<sub>o</sub> = 27.3 V; I<sub>o</sub> = 23 mA; P<sub>o</sub> = 157 mW; Characteristic: Linear
  • Reactances Ex ia IIC: L<sub>o</sub> = 61 mH; C<sub>o</sub> = 64 nF
  • Reactances Ex ia IIB: L<sub>o</sub> = 100 mH; C<sub>o</sub> = 552 nF
  • Ex ia IIA reactances: L<sub>o</sub> = 100 mH; C<sub>o</sub> = 2,28 F
  • Reactances Ex ia I: L<sub>o</sub> = 100 mH; C<sub>o</sub> = 2.95 F
  • Reactances: (The above-listed ratings do not account for the coincidental occurrence of capacitances and inductances. For ratings taking the coincidental occurrence of capacitances and inductances into account, see manual)
  • Marking: ATEX, IECEx, Underwriters Laboratories Inc.
Connection Data
  • Connection technology: In-/Outputs: 8 x CAGE CLAMP<sup></sup>
  • Connection type (1): Inputs/Outputs
  • Solid conductor: 0.08 ˜ 2.5 mm / 28 ˜ 14 AWG
  • Fine-stranded conductor: 0.08 ˜ 2.5 mm / 28 ˜ 14 AWG
  • Strip length: 8 ˜ 9 mm / 0.31 ˜ 0.35 inch
  • Anschlussanforderung zul¤ssige Leitungsl¤nge: 100 m
Geometrical Data
  • Width: 24 mm / 0.945 inch
  • Height: 67.8 mm / 2.669 inch
  • Height from upper-edge of DIN-35 rail: 60.6 mm / 2.386 inch
  • Depth: 100 mm / 3.937 inch
Mechanical Data
  • Type of mounting: DIN-35 rail
Material Data
  • Color: multicoloured
  • Housing material: Polycarbonate, polyamide 6.6
  • Fire load: 0.000 MJ
  • Weight: 91.988 g
  • Conformity marking: CE
Environmental Requirements
  • Surrounding air (operating) temperature: 0 ˜ 55 C
  • Surrounding air (storage) temperature: -40 ˜ 85 C
  • Protection class: IP20
  • Degree of pollution (5): 2 per IEC 61131-2
  • Operating altitude: 0 ˜ 2000 m
  • Mounting position: horizontal (standing/lying) or vertical
  • Relative air humidity (no condensation): 95 %
  • Vibration resistance: 4g per IEC 60068-2-6
  • Shock resistance: 15g per IEC 60068-2-27
  • EMC immunity to interference: acc. to EN 61000-6-2, marine applications
  • EMC emission of interference: acc. to EN 61000-6-3, marine applications
  • Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
  • Permissible H<sub>2</sub>S contaminant concentration at a relative humidity <lt/> 75 %: 10 ppm
  • Permissible SO<sub>2</sub> contaminant concentration at a relative humidity <lt/> 75 %: 25 ppm
Commercial data
  • Packaging type: BOX
  • Country of origin: DE
  • GTIN: 4050821531432
  • Customs Tariff No.: 85389099990
View AllClose