WAGO 857-500

(No reviews yet) Write a Review
SKU:
857-500
Condition:
New
configuration options:
DIP switch || WAGO Interface Configuration Software || WAGO Interface Configuration App
conformity marking:
CE
connection technology:
Push-in CAGE CLAMP
conversion time:
Peak-time measurement method (> 400 Hz): < 20 ms: Pulse time measurement method (< 400 Hz): < 200 s + TCycle duration
country of origin sales organisation germany:
DE
coupling:
AC/DC (adjustable: AC above 10 Hz)
depth from upper edge of din rail:
97.8 mm / 3.85 inch
emc emission of interference:
EN 61000-6-4
emc immunity to interference:
EN 61000-6-2
fine stranded conductor:
0.34 2.5 mm / 22 14 AWG
fire load:
0.762 MJ
height:
94 mm / 3.701 inch
hysteresis:
0.45 mA
input resistance:
10 k
input resistance 2:
¤ 600
input signal type:
Frequency generators || NAMUR sensors || NPN/PNP transistor outputs || Mechanical contact (dry contact)
input voltage max:
DC 31.2 V
load impedance current output:
¤ 600
load impedance voltage output:
2 k
measurement range frequency 1:
0.1 Hz 120 kHz
measurement range frequency 2:
0.1 Hz 1 kHz
measurement range frequency 3:
0.1 Hz 20 kHz
measurement span 1 min:
10 Hz
measurement span 2 min:
10 Hz
measurement span 3 min:
100 Hz
mounting type:
DIN-35 rail
nominal supply voltage us:
DC 24 V
npn residual voltage:
¤ 1.5 V
open circuit voltage:
DC 5 V
operating altitude max:
2000 m
output signal current:
0 10 mA: 2 10 mA: 0 20 mA: 4 20 mA
output signal type:
Current || Voltage
output signal voltage:
0 5 V: 1 5 V: 0 10 V: 2 10 V
packaging type:
Bag
pnp switching voltage:
7.5 V (+ residual voltage UCE sat)
power consumption at nominal supply voltage:
¤ 40 mA
power supply type:
24 VDC
pulse length 2:
500 s
pulse length 3:
25 s
relative humidity:
5 95 % (no condensation permissible)
sensor supply:
DC 8.2 V
sensor type 1:
Frequency generator || NPN/PNP transistor output with pull-up or pull-down resistor
sensor type 2:
NAMUR sensor (DIN EN 50227)
sensor type 3:
NPN/PNP transistor output without pull-up or pull-down resistor || Mechanical contact (dry contact)
short circuit monitoring:
4.7 mA
signal current 0:
¤ 1.2 mA
signal current 1:
2.1 mA
signal form:
Any
signal level:
1.5 V: 10 V: 20 V (switchable)
solid conductor:
0.08 2.5 mm / 28 14 AWG
standards specifications:
EN 61373
strip length:
9 10 mm / 0.35 0.39 inch
supply voltage range:
30 %
surrounding air temperature operation:
-25 70 C
surrounding air temperature storage:
-40 85 C
temperature coefficient:
¤ 0.01 %/K
test voltage input output supply:
AC 2.5 kV: 50 Hz: 1 min
transmission error typ:
¤ 0.1 % of upper-range value
weight:
36.200 g
width:
6 mm / 0.236 inch
wire break monitoring:
¤ 0.2 mA
  • Wago 857-500
  • Wago 857-500
  • Wago 857-500
  • Wago 857-500
$360.40

Description

F-TRANSDUCERUI

  • PC configuration interface
  • Signal acquisition from NAMUR, NPN or PNP sensors
  • Calibrated measurement range switching
  • Safe 3-way isolation with 2.5 kV test voltage per EN 61140
View AllClose