Schneider Electric

Schneider Electric LC1D18JD IEC contactor, TeSys Deca, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 12VDC coil, open

(No reviews yet) Write a Review
SKU:
LC1D18JD
MPN:
LC1D18JD
Condition:
New
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Compatibility Code:
LC1D
Average Impedance:
2.5 mOhm - Ith 32 A 50 Hz for power circuit
Rohs Exemption Information:
Yes
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Width:
45 mm
Pvc Free:
Yes
Rated Breaking Capacity:
300 A at 440 V for power circuit conforming to IEC 60947
Operating Time:
63±15 % ms closing || 20±20 % ms opening
Power Dissipation Per Pole:
2.5 W AC-1 || 0.8 W AC-3 || 0.8 W AC-3e
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Auxiliary Contact Composition:
1 NO + 1 NC
Inrush Power In W:
5.4-5.4 W 20°C)
Minimum Switching Current:
5 mA for Signaling circuit
Poles Description:
3P
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Electrical Durability:
1.65 Mcycles 18 A AC-3 <= 440 V || 1 Mcycles 32 A AC-1 <= 440 V || 1.65 Mcycles 18 A AC-3e <= 440 V
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Height:
77 mm
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Product Or Component Type:
contactor
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
Maximum Horse Power Rating:
1 hp at 115 V AC 50/60 Hz for 1 phase motors || 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 5 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 460/480 V AC 50/60 Hz for 3 phase mot
Signaling Circuit Frequency:
25...400 Hz
Contactor Application:
resistive load || motor control
Net Weight:
0.49 kg
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Country of Origin:
United States
[Uc] Control Circuit Voltage:
12 V DC
Device Short Name:
LC1D
Time Constant:
28 ms
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Depth:
95 mm
Pollution Degree:
3
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Weight:
0.49 kg
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Overvoltage Category:
III
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Control Circuit Type:
DC standard
Eu Rohs Directive:
Compliant with Exemptions
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 32 A (at 60°C) for power circuit
Protective Treatment:
THIEC 60068-2-30
$170.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.08 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose