Schneider Electric

Schneider Electric LC1G150EHEA Contactor, high power, TeSys Giga, advanced version, AC-3, <= 440V, 150A, 3 pole/NO, 48-130VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G150EHEA
MPN:
LC1G150EHEA
Condition:
New
Weight:
4.1 kg
Pvc Free:
Yes
Operating Time:
40...70 ms closing || 15...50 ms opening
Mercury Free:
Yes
Inrush Power In Va:
260-260 VA
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Motor Power Kw:
37 kW at 230 V AC 50/60 Hz (AC-3e) || 75 kW at 400 V AC 50/60 Hz (AC-3e) || 75 kW at 415 V AC 50/60 Hz (AC-3e) || 90 kW at 440 V AC 50/60 Hz (AC-3e) || 90 kW at 500 V AC 50/60 Hz (AC-3e) || 90 kW at 690 V AC 50/60 Hz (AC-3e) || 75 kW at 1000 V AC 50/
Width:
108 mm
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
[Ie] Rated Operational Current:
275 A (at <40°C) at <= 1000 V AC-1 || 150 A (at <60°C) at <= 440 V AC-3
Range:
TeSys
Associated Fuse Rating:
160 A aM at <= 440 V for motor || 160 A aM at <= 690 V for motor || 315 A gG at <= 690 V
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Ambient Air Temperature For Operation:
-25-60°C
Circularity Profile:
ENVEOLI2105013
Auxiliary Contact Composition:
1 NO + 1 NC
Contactor Application:
power switching || motor control
Mounting Support:
plate
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
[Uc] Control Circuit Voltage:
48...130 V AC 50/60 Hz || 48...130 V DC
Net Weight:
4.1 kg
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Environmental Disclosure:
ENVPEP2105013
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Maximum Horse Power Rating:
40 hp at 200/208 V 60 Hz || 50 hp at 230/240 V 60 Hz || 100 hp at 460/480 V 60 Hz || 125 hp at 575/600 V 60 Hz
Tightening Torque:
18 N.m
Product Or Component Type:
contactor
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Connection Pitch:
35 mm
Power Dissipation Per Pole:
10 W AC-1 - Ith 275 A || 5 W AC-3 - Ith 150 A
Depth:
193 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Pole Contact Composition:
3 NO
Average Impedance:
0.00018 Ohm
Color:
dark grey
Protective Treatment:
TH
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
China Rohs Regulation:
X
Range Of Product:
TeSys Giga
[Ui] Rated Insulation Voltage:
1000 V
Hold-In Power Consumption In Va:
8.9-8.9 VA
Sustainable Offer Status:
Green Premium product
Hold-In Power Consumption In W:
5.0-5.0 W
Eu Rohs Directive:
Compliant with Exemptions
Device Short Name:
LC1G
Ambient Air Temperature For Storage:
-60-80°C
[Icw] Rated Short-Time Withstand Current:
1.2 kA - 10 s || 0.7 kA - 30 s || 0.6 kA - 1 min || 0.45 kA - 3 min || 0.35 kA - 10 min
Rated Breaking Capacity:
1280 A at 440 V
$850.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 150A 90kW@440V. It provides a 48-130V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose