Schneider Electric LC1K1201F7 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 12 A, 1 NC aux., 110VAC coil
Schneider Electric
$86.00
LC1K1201F7 is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 12A AC-3 5.5kW@400V, it includes a 110V 50/60Hz AC coil and 1NC auxiliary contact. LC1K1201F7 is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 5.5kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it includes a 110V 50/60Hz AC coil and 1NC built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Provides a control circuit compatible with 50Hz and 60Hz supplies and 1NC built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
- [Ie] Rated Operational Current:
- 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
- Signaling Circuit Frequency:
- <= 400 Hz
- Sustainable Offer Status:
- Green Premium product
- Maximum Operating Rate:
- 3600 cyc/h
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- [Icw] Rated Short-Time Withstand Current:
- 115 A 50°C - 1 s for power circuit || 105 A 50°C - 5 s for power circuit || 100 A 50°C - 10 s for power circuit || 75 A 50°C - 30 s for power circuit || 55 A 50°C - 1 min for power circuit || 50 A 50°C - 3 min for power circuit || 25 A 50°C - >= 15 m
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
- Eu Rohs Directive:
- Compliant
- Reach Free Of Svhc:
- Yes
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- Range:
- TeSys
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Depth:
- 57 mm
- Contactor Application:
- resistive load || motor control
- Control Circuit Type:
- AC 50/60 Hz
- Mercury Free:
- Yes
- Environmental Disclosure:
- ENVPEP1503003EN
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Auxiliary Contacts Type:
- instantaneous 1 NC
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Non Overlap Distance:
- 0.5 mm
- Hold-In Power Consumption In Va:
- 4.5-4.5 VA (at 20°C)
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Rated Breaking Capacity:
- 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
- Rohs Exemption Information:
- Yes
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Auxiliary Contact Composition:
- 1 NC
- Warranty:
- 18 months
- Device Application:
- control
- Circularity Profile:
- ENVEOLI1503003EN
- Product Or Component Type:
- contactor
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Device Short Name:
- LC1K
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Pole Contact Composition:
- 3 NO
- Utilisation Category:
- AC-3 || AC-3e || AC-1 || AC-4
- Sustainable Packaging:
- Yes
- Width:
- 45 mm
- Country of Origin:
- Indonesia
- Overvoltage Category:
- III
- Irms Rated Making Capacity:
- 144 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947