null

Leuze MSI-SR-LC31MR-01 Safety relay

Leuze
SKU:
MSI-SR-LC31MR-01
$236.39
(No reviews yet) Write a Review
Condition:
New
Current Stock:
MSI-SR-LC31MR-01 Safety relay
Series:
MSI-SR-LC31
Application:
E-Stop circuits,Optoelectronic protective devices,Position switches (mechanical contacts),Solenoid switches (reed contacts, equivalent),Transponder switches (OSSD outputs)
Functions:
Cross circuit monitoring
Restart:
Manual
SIL:
3, IEC 61508
SILCL:
3, IEC/EN 62061
Performance Level (PL):
e, EN ISO 13849-1
PFHD:
3E-08 per hour
Mission time:
20 years, EN ISO 13849-1
Category:
4, EN ISO 13849-1
Continuous current per current path, max.:
8 A
Supply voltage UB:
24 V, AC/DC, -15 ... 10 %
Power consumption, max.:
1.6 W, For 24 V, plus output load
Nominal voltage UN:
24 V
Nominal frequency:
50 ... 60 Hz
Rated control supply voltage US at AC 60 Hz:
20.4 V
Rated control supply voltage US at AC 50 Hz:
26.4 V
Max. rated control supply voltage at AC 50 Hz:
26.4 V
Min. rated control supply voltage US at AC 50 Hz:
20.4 V
Min. rated control supply voltage US at DC:
20.4 V
Max. rated control supply voltage at DC:
26.4 V
Min. rated control supply voltage at DC:
20.4 V
Rated power AC:
2.9 V·A
Rated power DC:
1.6 W
Galvanic isolation between supply and control circuit:
Yes (when UN ? AC 42-48 V, AC 115-230 V, AC 230 V)
Number of outputs, safety-oriented, non-delayed, contact-based:
3 Piece(s)
Number of outputs, safety-oriented, delayed, contact-based:
0 Piece(s)
Number of outputs, signaling function, non-delayed, contact-based:
1 Piece(s)
Release current paths:
NO
Signaling current paths:
NC
Contact material:
Ag alloy, gold-plated
Usage category AC-15 (NO contact):
Ue 230V, Ie 3A
Usage category DC-13 (NO contact):
Ue 24V, Ie 3A
Short circuit protection (NO contact):
gG class safety fuse 6A, melting integral
Nominal switching voltage, release current paths AC:
230 V
Nominal switching voltage, signaling current paths AC:
230 V
Max. thermal continuous current Ith, release current paths:
8 A
Max. thermal continuous current Ith, signaling current paths:
5 A
Max. total current I² of all current paths:
25 A²
Mechanical life time:
100,000,000 switching cycles
Evaluation of the inputs:
Two-channel
Nominal output voltage DC:
24 V
Input current at the control inputs (safety circuit/reset circuit):
25 mA
Max. peak current at the control inputs (safety circuit/reset circuit):
100 mA
Max. cable resistance, per channel:
? (5 + (1.176 x UB / UN - 1) x 100) ?
Minimum switch-on time:
100 ms
Response time (manual start tA1):
100 ms
Test pulse time permitted tTP:
1 ms
Release time tR:
10 ms
Recovery time tW:
750 ms
Regression delay:
10 ms
Number of connections:
1 Piece(s)
Function:
Signal IN,Signal OUT,Voltage supply
Type of connection:
Terminal
Type of terminal:
Screw terminal
No. of pins:
16 -pin
Connection cross sections:
1 x 0.2 to 2.5 mm², wire,1 x 0.25 to 2.5 mm², wire with wire-end sleeve,2 x 0.2 to 1.0 mm², wire,2 x 0.25 to 1.0 mm², wire with wire-end sleeve
Dimension (W x H x L):
22.5 mm x 96.5 mm x 114 mm
Net weight:
210 g
Housing color:
Gray
Type of fastening:
Snap-on mounting
Ambient temperature, operation:
-25 ... 65 °C
Approvals:
TÜV Rheinland,c UL US
Customs tariff number:
85364900
ECLASS 5.1.4:
27371800
ECLASS 8.0:
27371819
ECLASS 9.0:
27371819
ECLASS 10.0:
27371819
ECLASS 11.0:
27371819
ECLASS 12.0:
27371819
ECLASS 13.0:
27371819
ECLASS 14.0:
27371819
ECLASS 15.0:
27371819
ETIM 5.0:
EC001449
ETIM 6.0:
EC001449
ETIM 7.0:
EC001449
ETIM 8.0:
EC001449
ETIM 9.0:
EC001449
ETIM 10.0:
EC001449
Datasheet:
View
Brochure:
View
Declaration of Conformity:
View