Schneider Electric ATS22D47Q soft starter for asynchronous motor, Altistart 22, control 230V, 230 to 440V, 11 to 22kW
Schneider Electric
$943.20
This soft starter can feed 3-phase asynchronous motors in supply line or delta connection. It has a rating of 47A and 230V to 440V, a rated power up to 22kW (400V to 440V in supply line) and up to 45kW (400V to 440V in motor delta connection). It is designed for simple and complex machines such as centrifugal and piston pumps, fans, screw compressors and material handling equipment. Slim form factor improves versatility; allows mounting in frames of any kind of machines. It features an Integrated bypass, this reduces noise and decreases heat dissipation. Compatibility with SoMove software allows configurations and settings to be easily transferred, meaning spares can be quickly installed. It provides smooth starting for your machinery, avoiding mechanical stresses and extending their service life.
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Net Weight:
- 7 kg
- Power Range:
- 7-11 kW 200-240 V 3 phase || 15-25 kW 380-440 V 3 phase
- Physical Interface:
- RS485 multidrop
- Ambient Air Temperature For Operation:
- -10-40°C without derating) || 40-60°C with current derating 2.2 % per°C)
- Product Or Component Type:
- soft starter
- Discrete Input Voltage:
- 24 V <= 30 V
- Pollution Degree:
- level 2 IEC 60664-1
- China Rohs Regulation:
- X
- Product Certifications:
- CCC || C-tick || UL || GOST || CSA
- Type Of Start:
- start with torque control (current limited to 3.5 In)
- Discrete Input Number:
- 3
- Installed Device:
- 31
- Product Destination:
- asynchronous motors
- Output Current:
- 0.4...1 Icl adjustable
- Operating Altitude:
- <= 3280.84 ft (1000 m) without derating || > 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 m
- Connector Type:
- 1 RJ45
- Motor Starter Type:
- soft starter
- Discrete Output Type:
- relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O || relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
- Communication Port Protocol:
- Modbus
- Motor Power Kw:
- 11 kW 230 V || 22 kW 400 V || 22 kW 440 V
- Vibration Resistance:
- 1 gn 13-200 Hz)IEC 60068-2-6 || 1.5 mm 2-13 Hz)IEC 60068-2-6
- Assembly Style:
- with heat sink
- Noise Level:
- 45 dB
- Relative Humidity:
- 0-95 % without condensation or dripping water IEC 60068-2-3
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Depth:
- 169 mm
- [Uc] Control Circuit Voltage:
- 230 V - 15...10 % 50/60 Hz
- Height:
- 265 mm
- Discrete Output Number:
- 2
- Operating Position:
- vertical +/- 10 degree
- Factory Setting Current:
- 42 A
- Icl Starter Rating:
- 47 A connection in the motor supply line for standard applications
- Marking:
- CE
- Weight:
- 7 kg
- Ambient Air Temperature For Storage:
- -25-70°C
- [Us] Rated Supply Voltage:
- 230...440 V - 15...10 %
- Device Connection:
- to the motor delta terminals || in the motor supply line
- Maximum Switching Current:
- 5 A 250 V AC resistive 1 relay outputs || 5 A 30 V DC resistive 1 relay outputs || 2 A 250 V AC inductive 0.4 20 ms relay outputs || 2 A 30 V DC inductive 7 ms relay outputs
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Power Dissipation In W:
- 48 W for standard applications
- Mercury Free:
- Yes
- Function Available:
- internal bypass
- Component Name:
- ATS22
- Phase:
- 3 phase
- Control Circuit Consumption:
- 20 W
- Minimum Switching Current:
- 100 mA 12 V DC relay outputs)
- Protection Type:
- phase failure line || thermal protection motor || thermal protection starter
- Discrete Input Logic:
- positive logic LI1, LI2, LI3 < 5 V <= 2 mA > 11 V, >= 5 mA
- Utilisation Category:
- AC-53A