Schneider Electric ATV212H075N4 Atv212 0,75Kw 1Hp 480V Tri Cem Ip20

(No reviews yet) Write a Review
SKU:
ATV212H075N4
UPC:
3606480322440
Condition:
New
Type Of Cable:
without mounting kit 1 IEC cable 45 °C, copper 90 °C / XLPE/EPR || without mounting kit 1 IEC cable 45 °C, copper 70 °C / PVC || with UL Type 1 kit 3 UL 508 cable 40 °C, copper 75 °C / PVC
Depth:
150 mm
Data Format:
8 bits, 1 stop, odd even or no configurable parity
Supply Frequency:
50...60 Hz - 5...5 %
Isolation:
electrical between power and control
Phase:
3 phase
Warranty:
18 months
Transmission Frame:
RTU
Net Weight:
2 kg
Assembly Style:
with heat sink
Tightening Torque:
1.3 N.m, 11.5 lb.in L1/R, L2/S, L3/T) || 0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
Line Current:
1.4 A 480 V || 1.7 A 380 V
Continuous Output Current:
2.2 A 380 V || 2.2 A 460 V
Communication Service:
read device identification (43) || time out setting from 0.1 to 100 s || write single register (06) || write multiple registers (16) 2 words maximum || monitoring inhibitable || read holding registers (03) 2 words maximum
Rohs Exemption Information:
Yes
Motor Starter Type:
variable speed drive
Connector Type:
1 open style || 1 RJ45
Width:
107 mm
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Discrete Output Type:
configurable relay logic FLA, FLC) NO - 100000 cycles || configurable relay logic FLB, FLC) NC - 100000 cycles || configurable relay logic RY, RC) NO - 100000 cycles
Braking To Standstill:
by DC injection
Discrete Output Number:
2
Maximum Horse Power Rating:
1 hp
Discrete And Process Manufacturing:
building - HVAC compressor for scroll || building - HVAC fan || building - HVAC pump
Analogue Output Number:
1
Network Frequency:
47.5...63 Hz
Analogue Output Type:
FM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bits || FM switch-configurable current 0...20 mA 970 Ohm 10 bits
China Rohs Regulation:
X
Device Short Name:
ATV212
Emc Filter:
Class C2 EMC filter integrated
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Physical Interface:
2-wire RS 485
Response Time:
FM 2 ms +/- 0.5 ms analog || FLA, FLC 7 ms +/- 0.5 ms discrete || FLB, FLC 7 ms +/- 0.5 ms discrete || RY, RC 7 ms +/- 0.5 ms discrete
Option Card:
communication card LonWorks
Pollution Degree:
2 IEC 61800-5-1
Dielectric Strength:
3535 V DC between earth and power terminals || 5092 V DC between control and power terminals
Motor Power Kw:
0.75 kW
Motor Slip Compensation:
not available in voltage/frequency ratio motor control || automatic whatever the load || adjustable
Protection Type:
overheating protection drive || thermal power stage drive || short-circuit between motor phases drive || input phase breaks drive || overcurrent between output phases and earth drive || overvoltages on the DC bus drive || break on the control circuit
Operating Position:
vertical +/- 10 degree
Relative Humidity:
5-95 % without condensation IEC 60068-2-3 || 5-95 % without dripping water IEC 60068-2-3
Speed Accuracy:
+/- 10 % of nominal slip 0.2 Tn to Tn
Torque Accuracy:
+/- 15 %
Ambient Air Temperature For Operation:
-10-40 °C without derating) || 40-50 °C with derating factor)
Operating Altitude:
3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m || <= 3280.84 ft (1000 m) without derating
[Us] Rated Supply Voltage:
380...480 V - 15...10 %
Ambient Air Temperature For Storage:
-25-70 °C
Specific Application:
HVAC
Transmission Rate:
9600 bps or 19200 bps
Marking:
CE
Insulation Resistance:
>= 1 mOhm 500 V DC for 1 minute
Standards:
EN 55011 class A group 1 || IEC 61800-3 environments 1 category C3 || IEC 61800-3 environments 2 category C2 || IEC 61800-3 environments 2 category C1 || EN 61800-3 category C3 || IEC 61800-3 environments 1 category C2 || IEC 61800-3 environments 2 c
Functionality:
mid
Electrical Connection:
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 2.5-2.5 mm² / AWG 14 || L1/R, L2/S, L3/T terminal 6-6 mm² / AWG 10
Product Specific Application:
pumps and fans in HVAC
Speed Drive Output Frequency:
0.5-200 Hz
Frequency Resolution:
display unit 0.1 Hz || analog input 0.024/50 Hz
Supply:
internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection || internal supply 24 V DC 21-27 V), <200 A overload and short-circuit protection
Discrete Input Logic:
positive logic (source) F, R, RES), <= 5 V, >= 11 V || negative logic (sink) F, R, RES), >= 16 V, <= 10 V
Sampling Duration:
2 ms +/- 0.5 ms F discrete || 2 ms +/- 0.5 ms R discrete || 2 ms +/- 0.5 ms RES discrete || 3.5 ms +/- 0.5 ms VIA analog || 22 ms +/- 0.5 ms VIB analog
Analogue Input Number:
2
Range Of Product:
Altivar 212
Environmental Characteristic:
classes 3C1 IEC 60721-3-3 || classes 3S2 IEC 60721-3-3
Analogue Input Type:
VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits || VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits || VIB configurable PTC probe 0...6 probes 1500 Ohm || VIA switch-configurable current 0...20 mA 250 Ohm 10 bits
Vibration Resistance:
1.5 mm 3-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)EN/IEC 60068-2-8
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Power Range:
0.55-1 kW 380-440 V 3 phase || 0.55-1 kW 480-500 V 3 phase
Maximum Switching Current:
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R) || 5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R) || 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R) || 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R)
Minimum Switching Current:
3 mA 24 V DC configurable relay logic
Product Or Component Type:
variable speed drive
Linearity Error:
VIA +/- 0.15 % of maximum value input || VIB +/- 0.15 % of maximum value input || FM +/- 0.2 % output
Type Of Polarization:
no impedance
Speed Range:
45301
Communication Port Protocol:
Modbus || METASYS N2 || APOGEE FLN || LonWorks || BACnet
Height:
143 mm
Product Certifications:
UL || NOM 117 || CSA || C-tick
Prospective Line Isc:
5 kA
Acceleration And Deceleration Ramps:
automatic based on the load || linear adjustable separately from 0.01 to 3200 s
Output Voltage:
<= power supply voltage
Air Flow:
19 m3/h
Discrete Input Type:
F programmable 24 V DC level 1 PLC 4700 Ohm || R programmable 24 V DC level 1 PLC 4700 Ohm || RES programmable 24 V DC level 1 PLC 4700 Ohm
Mercury Free:
Yes
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Destination:
asynchronous motors
Transient Overtorque:
120-120 % of nominal motor torque +/- 10 % 60 s
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Noise Level:
51 dB 86/188/EEC
Power Dissipation In W:
55 W
Nominal Switching Frequency:
12 kHz
Supply Voltage Limits:
323-528 V
Switching Frequency:
6...16 kHz adjustable || 12...16 kHz with derating factor
Number Of Addresses:
1-247
Apparent Power:
1.6 kVA 380 V
Maximum Transient Current:
2.4 A 60 s
Accuracy:
+/- 0.6 % VIA) for a temperature variation 60 °C || +/- 0.6 % VIB) for a temperature variation 60 °C || +/- 1 % FM) for a temperature variation 60 °C
Asynchronous Motor Control Profile:
voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) || voltage/frequency ratio - Energy Saving, quadratic U/f || voltage/frequency ratio, 2 points || flux vector control without sensor, standard || voltage/frequency ratio, 5 point
Ip Degree Of Protection:
IP20 on upper part without blanking plate on cover IEC 61800-5-1 || IP20 on upper part without blanking plate on cover IEC 60529 || IP21 IEC 61800-5-1 || IP21 IEC 60529 || IP41 on upper part IEC 61800-5-1 || IP41 on upper part IEC 60529
Regulation Loop:
adjustable PI regulator
Ip Degree Of Protection:
IP21
Local Signalling:
for DC bus energized 1 LED (red)
Brochure:
View
Catalog:
View
Datasheet:
View
$691.73

Description

This Altivar 212 variable speed drive can feed 3-phase asynchronous motors. Its protection index is IP21 and it has a built-in EMC filter. It works at a rated power up to 0.75kW / 1hp and a rated voltage from 380V to 480V AC. Its design is based on eco-energy with a reduction in energy consumption of up to 70% compared to a conventional control system. Thanks to its cable temperature rise reduction technology, the Altivar 212 drive offers immediate, disturbance-free operation avoiding additional options such as a line choke or DC choke to deal with current harmonics. It weighs 2kg and its dimensions are, 107mm wide, 143mm high, 150mm deep. It is specifically designed for the most common fluid management applications in tertiary sector buildings (HVAC) like heating, ventilation, air conditioning and pumping. It conforms to international standards IEC/EN 61800-5-1 and IEC/EN 61800-3 (immunity and conducted and radiated EMC emissions). It is also CE, UL, CSA, C-Tick and NOM certified. The Altivar 212 offers optional motor chokes which can increase the maximum cable lengths between the drive and the motor and limit disturbance at the motor terminals. It is designed to be mounted in vertical position (+/- 10 °) on a panel, thanks to 4 fixing holes. It can also be mounted directly on a 35 mm wide DIN rail, thanks to the kit VW3A31852, to order separately. The Altivar 212 drive can easily be adapted to all building management systems thanks to its numerous functions and communication protocols integrated as standard, Modbus, METASYS N2, APOGEE FLN P1 and BACnet.